Commissioning
EL125x, EL2258
124
Version: 2.5
Remedy:
- Set the channel to asynchronous mode, so that the events are retrieved in handshake mode.
or
- Track event timestamp no. 1 in the online display:
Fig. 159: Timestamp via online display
5. Processing of events in the PLC
The channel supplies 32-bit timestamp. The following function block can be used for scaling up to the
convenient 64-bit format:
Download (https://infosys.beckhoff.com/content/1033/el125x_el2258/Resources/zip/1885941003.zip)
6.5.3
Commissioning in compatibility mode
The multi-timestamp terminals can also be operated in compatibility mode with regard to the EL1252. The
following settings are required:
Procedure:
- The changeover should only be implemented via the
predefined PDO
: