Commissioning
EL125x, EL2258
125
Version: 2.5
Fig. 160: Predefined PDOs for compatibility mode
- Via the CoE 0x80n0:0 TSI Settings (n = 8 ... F) the response for several events in a single cycle can be
specified here. This is comparable to the EL1252. In this case MTSF =1.
0x80n0:0 TSI Set-
tings Ch. n=8...F
Name
Entry
Description
80n0:01
Pos
Sample
Mode
Defines the behavior for rising edges with several signals per
cycle
80n0:01
FALSE
Last edge The last detected event is forwarded to the PLC
80n0:01
TRUE
First edge The first detected event is forwarded to the PLC
80n0:02
Neg
Sample
Mode
Defines the behavior for falling edges with several signals per
cycle
80n0:02
FALSE
Last edge The last detected event is forwarded to the PLC
80n0:02
TRUE
First edge The first detected event is forwarded to the PLC
Note
Free PDO selection
No provision is made for free arrangement of the respective PDOs in compatibility mode.
6.6
Commissioning outputs
Table of contents
•
Basic principles [
}
126]
•
Commissioning an MTO channel [
}
130]
-
1. How do I test my actuator? [
}
130]
-
2. Setting the multi-timestamping factor (MTSF) [
}
131]
-
3. How are the outputs with timestamp activated? [
}
131]
•
Commissioning in compatibility mode EL2252 [
}
132]
Содержание EL1258
Страница 2: ......
Страница 6: ...Table of contents EL125x EL2258 6 Version 2 5...
Страница 42: ...Mounting and wiring EL125x EL2258 42 Version 2 5 Fig 36 Other installation positions...
Страница 76: ...Commissioning EL125x EL2258 76 Version 2 5 Fig 86 Incorrect driver settings for the Ethernet port...