Commissioning
EL125x, EL2258
177
Version: 2.5
Index 6pp1 MTI inputs (for 08 ≤ pp ≤ 0F; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
6pp1:0
MTI inputs
UINT8
RO
0x00 (0
dec
)
6pp1:01
No of input events
Signals the number of new timestamps available in the
process image. If three is returned, for example, only
the objects "Input event state 1...3" and "Input event
time 1...3" are valid.
UINT8
RO
0x00 (0
dec
)
6pp1:09
Input state
Indicates the current input state at the time of the
process data cycle.
BOOLEAN
RO
0x00 (0
dec
)
6pp1:0A
Input buffer overflow
More events occurred at the input than elements were
free in the buffer for the channel.
BOOLEAN
RO
0x00 (0
dec
)
6pp1:0F
Input cycle counter
Is incremented with each process data cycle and
switches to 0 after its maximum value of 3.
BIT2
RO
0x00 (0
dec
)
6pp1:11
Events in input buffer
Signals the number of events currently in the buffer.
UINT8
RO
0x00 (0
dec
)
6pp1:12
Input order feedback
This byte reflects the state of the "Input order counter"
byte
(further explanation see here) [
}
122]
.
UINT8
RO
0x00 (0
dec
)
6pp1:21
Input event state 1
Indicates whether the event was a rising (1) or a falling
(0) edge.
BOOLEAN
RO
0x00 (0
dec
)
6pp1:2A
Input event state 10
BOOLEAN
RO
0x00 (0
dec
)
6pp1:41
Input event time 1
32-bit timestamp for the corresponding "Input event
state n"
UINT32
RO
0x00000000
(0
dec
)
6pp1:4A
Input event time 10
UINT32
RO
0x00000000
(0
dec
)
Index 6pp0 TSO Inputs (for 10 ≤ pp ≤ 17; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
6pp0:0
TSO Inputs
UINT8
RO
0x00 (0
dec
)
6pp0:01
Feedback
Indicates the current output state
BOOLEAN
RO
0x00 (0
dec
)
Index 6pp0 TSI Inputs (for 18 ≤ pp ≤ 1F; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
6pp0:0
TSI Inputs
UINT8
RO
0x00 (0
dec
)
6pp0:01
Input
Current input status
BOOLEAN
RO
0x00 (0
dec
)
6pp0:09
Status
Bit 0: Is set for one cycle if a rising edge was detected.
Bit 1: Is set for one cycle if a falling edge was detected.
UINT8
RO
0x00 (0
dec
)
6pp0:41
LatchPos
Timestamp of the rising edge
UINT64
RO
6pp0:42
LatchNeg
Timestamp of the falling edge
UINT64
RO
Index F611 DEV Inputs
Index (hex) Name
Meaning
Data type
Flags
Default
F611:0
DEV Inputs
UINT8
RO
0x00 (0
dec
)
F611:02
Undervoltage Up
The nominal voltage at the power contacts was signifi-
cantly below the minimum value.
BOOLEAN
RO
0x00 (0
dec
)
F611:03
Overtemperature
Overtemperature fault: The temperature of the input or
output blocks is too high. For output terminals check
whether one of the channels is affected by a short cir-
cuit.
BOOLEAN
RO
0x00 (0
dec
)
F611:04
Checksum error
An error occurred in the internal data transfer
BOOLEAN
RO
0x00 (0
dec
)
F611:21
SysTime
DC timestamp of the last input mapping. This time-
stamp should not be used as reference
(information
on DC reference times). [
}
133]
UINT64