Commissioning
EL125x, EL2258
119
Version: 2.5
• “Multi-timestamp PDOs” and “compatible PDOs” cannot be combined
• The corresponding control/status must be active for each active input/output channel
• The MTSF can be set freely from 1 to 10 for each channel
• Only 1 multi-timestamp factor may be active per channel. It is therefore not permitted to activate PDO
"MTO Outputs 5x Channel 1" and PDO "MTO Outputs 2x Channel 1" at the same time, for example.
If an irregular PDO combination is selected, it may lead to the ERR-PREOP state ‘invalid output mapping’ or
‘invalid input mapping’.
Fig. 151: Event logger message from the System Manager in the event of invalid PDO combination
6.5
Commissioning inputs
Table of contents
•
Basic principles [
}
119]
•
Commissioning an MIT channel [
}
122]
-
1. Synchronous or asynchronous operation? [
}
122]
-
2. Setting the multi-timestamping factor (MTSF) [
}
122]
-
3. When should the filter in CoE be activated? (default: deactivated) [
}
123]
-
4. How can I test the input channel? [
}
123]
-
5. Processing of events in the PLC [
}
124]
•
Commissioning in compatibility mode [
}
124]
The section below describes commissioning of a digital input terminal with multi-timestamp function at a
PLC.
6.5.1
Basic principles
Each MTI channel (multi-timestamp input) has inputs and outputs in the cyclic process image, which have to
be linked with the PLC/task.