Commissioning
EL125x, EL2258
186
Version: 2.5
Index 1606 MTO RxPDO-Map Outputs 2x Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
1606:0
MTO RxPDO-Map
Outputs 2x Ch.2
PDO Mapping RxPDO 7
UINT8
RO
0x0D (13
dec
)
1606:01
SubIndex 001
1. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x01 (Output buffer reset))
UINT32
RO
0x7011:01, 1
1606:02
SubIndex 002
2. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x02 (Manual output state))
UINT32
RO
0x7011:02, 1
1606:03
SubIndex 003
3. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x03 (Force order))
UINT32
RO
0x7011:03, 1
1606:04
SubIndex 004
4. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x04 (Enable manual operation))
UINT32
RO
0x7011:04, 1
1606:05
SubIndex 005
5. PDO Mapping entry (4 bits align)
UINT32
RO
0x0000:00, 4
1606:06
SubIndex 006
6. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x09 (Output order counter))
UINT32
RO
0x7011:09, 8
1606:07
SubIndex 007
7. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x11 (No of output events))
UINT32
RO
0x7011:11, 8
1606:08
SubIndex 008
8. PDO Mapping entry (8 bits align)
UINT32
RO
0x0000:00, 8
1606:09
SubIndex 009
9. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x21 (Output event state 1))
UINT32
RO
0x7011:21, 1
1606:0A
SubIndex 010
10. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x22 (Output event state 2))
UINT32
RO
0x7011:22, 1
1606:0B
SubIndex 011
11. PDO Mapping entry (30 bits align)
UINT32
RO
0x0000:00, 30
1606:0C
SubIndex 012
12. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x41 (Output event time 1))
UINT32
RO
0x7011:41, 32
1606:0D
SubIndex 013
13. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x42 (Output event time 2))
UINT32
RO
0x7011:42, 32
Index 1607 MTO RxPDO-Map Outputs 1x Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
1607:0
MTO RxPDO-Map
Outputs 1x Ch.2
PDO Mapping RxPDO 8
UINT8
RO
0x0B (11
dec
)
1607:01
SubIndex 001
1. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x01 (Output buffer reset))
UINT32
RO
0x7011:01, 1
1607:02
SubIndex 002
2. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x02 (Manual output state))
UINT32
RO
0x7011:02, 1
1607:03
SubIndex 003
3. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x03 (Force order))
UINT32
RO
0x7011:03, 1
1607:04
SubIndex 004
4. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x04 (Enable manual operation))
UINT32
RO
0x7011:04, 1
1607:05
SubIndex 005
5. PDO Mapping entry (4 bits align)
UINT32
RO
0x0000:00, 4
1607:06
SubIndex 006
6. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x09 (Output order counter))
UINT32
RO
0x7011:09, 8
1607:07
SubIndex 007
7. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x11 (No of output events))
UINT32
RO
0x7011:11, 8
1607:08
SubIndex 008
8. PDO Mapping entry (8 bits align)
UINT32
RO
0x0000:00, 8
1607:09
SubIndex 009
9. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x21 (Output event state 1))
UINT32
RO
0x7011:21, 1
1607:0A
SubIndex 010
10. PDO Mapping entry (31 bits align)
UINT32
RO
0x0000:00, 31
1607:0B
SubIndex 011
11. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x41 (Output event time 1))
UINT32
RO
0x7011:41, 32