Commissioning
EL125x, EL2258
248
Version: 2.5
Index 6pp0 TSO Inputs (for 08 ≤ pp ≤ 0F; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
6pp0:0
TSO Inputs
UINT8
RO
0x00 (0
dec
)
6pp0:01
Feedback
Returns the current value of the output
BOOLEAN
RO
0x00 (0
dec
)
Index F611 DEV Inputs
Index (hex) Name
Meaning
Data type
Flags
Default
F611:0
DEV Inputs
UINT8
RO
0x00 (0
dec
)
F611:02
Undervoltage Up
The nominal voltage at the power contacts was signifi-
cantly below the minimum value.
BOOLEAN
RO
0x00 (0
dec
)
F611:03
Overtemperature
Overtemperature fault: The temperature of the input or
output blocks is too high. For output terminals check
whether one of the channels is affected by a short cir-
cuit.
BOOLEAN
RO
0x00 (0
dec
)
F611:04
Checksum error
An error occurred in the internal data transfer
BOOLEAN
RO
0x00 (0
dec
)
F611:21
SysTime
DC timestamp of the last input mapping. This time-
stamp should not be used as reference
(information
on DC reference times). [
}
133]
UINT64
RO
6.8.3.1.4
Output data
Index 7pp1 MTO outputs (for 00 ≤ pp ≤ 07; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
7pp1:0
MTO outputs
UINT8
RO
0x00 (0
dec
)
7pp1:01
Output buffer reset
Removes all elements from the buffer
Clearing can be achieved through a rising edge or con-
tinuously by applying 1 at this bit. The behavior can be
parameterized via CoE object
0x8pp1:11 [
}
247]
.
BOOLEAN
RO
0x00 (0
dec
)
7pp1:02
Manual output state
This bit can be used to switch the output without using
timestamps.
• Method 1: The CoE object
0x8pp1:02 [
}
247]
("Enable manual operation") is set to TRUE.
Timestamp mode is now switched off, and the
output can only be switched via the bit "Manual
operation state". This is particularly helpful for
the commissioning phase.
• Method 2: Via the bit "Enable manual
operation" (0x7pp1:04) the channel output can
be forced to the value of this object. Timestamp
processing continues in the background. Output
is only reactivated if the bit "Enable manual
operation" is set to 0 again.
BOOLEAN
RO
0x00 (0
dec
)
7pp1:03
Force order
This bit defines how to deal with timestamps that were
placed in the past
(see diagram) [
}
126]
.
BOOLEAN
RO
0x00 (0
dec
)
7pp1:04
Enable manual opera-
tion
See "Manual output state"
(0x7pp1:02) [
}
248]
.
BOOLEAN
RO
0x00 (0
dec
)
7pp1:09
Output order counter
Incrementing this byte indicates to the channel that
new output events can be accepted
UINT8
RO
0x00 (0
dec
)
7pp1:11
No of output events
Number of filled "Output event state" and "Output
event time" objects
UINT8
RO
0x00 (0
dec
)
7pp1:21
Output event state 1
This bit is used to specify which state the output should
assume at the time of "Output event time 1"
BOOLEAN
RO
0x00 (0
dec
)
7pp1:2A
Output event state 10
...
BOOLEAN
RO
0x00 (0
dec
)
7pp1:41
Output event time 1
Time at which the state described in "Output event
state 1" is to be applied
UINT32
RO
0x00000000
(0
dec
)
7pp1:4A
Output event time 10
...
UINT32
RO
0x00000000
(0
dec
)
Содержание EL1258