Specific functions of BML BM1/BM2 (continued)
8.2.3 Real time errors
The real time errors are displayed with the help of LEDs:
Real time errors
Possible cause
Troubleshooting
Nonius signal overdriven
Air gap between sensor module and magnetic disc/
magnetic tape is too great.
►
Check orientation of the sensor
module to the magnetic disk or
magnetic tape and/or repeat
calibration.
Nonius signal too low
The working range of the sensor module has been
exceeded or the magnetic disc/magnetic tape is
defective.
Master signal overdriven
Air gap between sensor module and magnetic disc/
magnetic tape is too great.
Master signal too low
The working range of the sensor module has been
exceeded or the magnetic disc/magnetic tape is
defective.
Plausibility error in period
counter
Plausibility check of the absolute signal fails or no
calibration performed.
ABZ frequency error
Calibration failed, sensor module defective.
►
Check supply voltage and/or
repeat calibration.
►
Replace sensor module.
Frequency counter of the
internal converter
Calibration failed, sensor module defective.
Tab. 8-5: Real-time errors of BML BM1/BM2
BAE PD-ML-010-04
Configuration Tool + USB-Adapter
Содержание BAE PD-ML-010-04
Страница 1: ...deutsch Configuration Tool USB Adapter english Configuration Tool USB Adapter BAE PD ML 010 04...
Страница 2: ...www balluff com...
Страница 3: ...BAE PD ML 010 04 Configuration Tool USB Adapter deutsch...
Страница 4: ...www balluff com...
Страница 39: ...BAE PD ML 010 04 Configuration Tool USB Adapter english...
Страница 40: ...www balluff com...
Страница 75: ......