18
english
6
Specific functions BML-S1G (continued)
Calibration Wizard
1.
Open the calibration window (see
chapter 6.1.5 on page 17), define the number of
poles on the ring and press <Enter> to start the
configuration process. Do not interrupt this process to
avoid malfunctions.
Fig. 6-3: Enter/change number of poles
2.
After the parameter calculation is done, you can start
the calibration process with the
Start
CaLiBratiOn
!
button.
3.
After the calibration is started, rotate the ring in the
forward direction at a constant and slow speed until
the
S
tOp
rOtatiOn
message is displayed. During the
forward movement, follow the instructions displayed in
the window (e.g. wrong direction).
4.
If the forward direction was successfully measured,
move backward with constant and slow speed until the
S
tOp
rOtatiOn
message is displayed. During the
backward movement, follow the instructions displayed
in the window.
5.
If the backward direction was also successfully
measured, the parameters will be updated in the BML.
Do not interrupt this process to avoid malfunctions.
6.
If the update succeeded, the following message
appears on the screen:
Fig. 6-4: Enter/change number of poles
Possible errors, troubleshooting
– Parameters (e.g. number of poles) are not correctly
defined or the mechanical settings (e.g. air gap, side
offset and tangential offset) are critical.
Fig. 6-5: Parameters not defined correctly or mechanical
settings not ideal
►
Check the parameters, adjust the mechanical
settings and repeat the calibration.
– At the end of the calibration procedure the message
ERROR. Calibration failed.
may appear and means that
the mechanical settings need to be corrected (e.g. air
gap, lateral and tangential offset).
►
Adjust the mechanical settings (e.g. set a smaller
air gap, side offset and tangential offset).
– Communication related and other errors
►
Check connections and refer to chapter 6.1.5 on
page 17.
Deleting calibration
The current calibration can be deleted by clicking on
DeLete
CaLiBratiOn
!
With this function the BML parameters
will be set back to linear operation.
Another option to clear the rotative calibration is to use the
built-in factory defaults function (see chapter 5.3.3 on
page 14).
Aborting calibration
The calibration can be aborted by clicking on
a
BOrt
in the
calibration window. The calibration will be aborted and the
BML parameters will be set back to linear operation.
BAE PD-ML-010-04
Configuration Tool + USB-Adapter
Содержание BAE PD-ML-010-04
Страница 1: ...deutsch Configuration Tool USB Adapter english Configuration Tool USB Adapter BAE PD ML 010 04...
Страница 2: ...www balluff com...
Страница 3: ...BAE PD ML 010 04 Configuration Tool USB Adapter deutsch...
Страница 4: ...www balluff com...
Страница 39: ...BAE PD ML 010 04 Configuration Tool USB Adapter english...
Страница 40: ...www balluff com...
Страница 75: ......