Azbil Corporation
Operation
Model SLX 110/120 - Smart displacement type level transmitter 2-11
Span adjustment
• The following procedure is based on water level adjustment.
1. Set specific gravity to 1 (water).
2. Set water 100%.
3. Carry out a span adjustment.
4.
Change the specific gravity to the specific gravity of the fluid to be measured.
~Note
•
When the fluid to be measured can be set to liquid level 100%, the
specific gravity need not be changed before and after the adjustment.
•
When the specific gravity of the fluid to be measured is lighter than
water, it is possible to carry out span adjustment without changing
specific gravity (conventional water level adjustment) by inputting the
liquid level for which specific gravity is converted beforehand (giving
100% equivalent buoyancy generated).
•
In the case of the level gauge, carry out span adjustment with the float
completed immersed in the liquid of the lower layer without changing
specific gravity.
Set the liquid level in the chamber to water 100%.
Step
Button
Procedure
SFC screen
1
B
CONF
Press [CONF].
SLX CONFIG
FUNCTION CONFIG ?
2
H
NEXT
or
L
PREV
press [NEXT] or [PREV] to display the
basic data setting screen.
SLX CONFIG
FUNCTION CONFIG ?
3
ENTER
( Yes )
NON-VOL
Press [ENTER].
SLX CONFIG
WORKING...
4
The current specific gravity set value is
displayed.
GRAVITY
0.9000
5
Enter value of 1 as specific gravity of
water.
GRAVITY
1_
Содержание SLX 110
Страница 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Страница 4: ......
Страница 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Страница 40: ...Installation Azbil Corporation 1 26 Model SLX 110 120 Smart displacement type level transmitter...
Страница 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Страница 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Страница 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Страница 163: ......
Страница 166: ......
Страница 168: ......