Azbil Corporation
Maintenance
Model SLX 110/120 - Smart displacement type level transmitter 3-29
n
Remove the board from the connector of the terminal block and replace the
terminal block.
Terminal block
Connector
Board
o
Assemble the terminal block into the instrument in the reverse order.
If the terminal block is assembled into the case, turn the terminal block so that the
lead wires are not caught and bind the lead wires together.
Recommended tightening torque of fixing screws, grounding screws: 1.2 +-0.1N
s
m
Attach a collar to the grounding screws.
3-9 : Starting instrument after maintenance