Maintenance
Azbil Corporation
3-20
Model SLX 110/120 - Smart displacement type level transmitter
Calibrating output signal 100%
Use the following procedure to set the output to 100% and calibrate so that the
reading of the ammeter becomes 20 mA.
Step
Button
Procedure
SFC screen
1
OUT- J
PUT
INPUT
Press [OUTPUT].
OUTPUT TAG-0001
WORKING...
i
OUTPUT TAG - 0001
0.00 %
2
V
1
Z
0
ACT PR
Z
0
ACT PR
Press numeric keys [1] [0] [0] in that
order.
OUTPUT TAG - 0001
100
3
ENTER
( Yes )
NON-VOL
Press [ENTER].
- This sets the instrument to a 20 mA
constant current source mode.
OUTPUT TAG-0001
WORKING...
i
OUTPUT TAG - 0001
100.00 % #
4
Make sure the ammeter indicates 20
mA.
OUTPUT TAG - 0001
100.00 % #
5
OUT- J
PUT
INPUT
Press [OUTPUT].
The current output is 100%.
OUTPUT TAG-0001
WORKING...
i
OUTPUT TAG - 0001
100.00 % #
Содержание SLX 110
Страница 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Страница 4: ......
Страница 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Страница 40: ...Installation Azbil Corporation 1 26 Model SLX 110 120 Smart displacement type level transmitter...
Страница 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Страница 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Страница 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Страница 163: ......
Страница 166: ......
Страница 168: ......