Страница 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...

Страница 2: ...aims the implied warranties of mer chantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer In no ev...

Страница 3: ...offers high performance and highly reliable level transmitters with a microprocessor incorporated in each one Most operations such as starting measurement reading of measured data check or change of...

Страница 4: ......

Страница 5: ...ality control program If you find any omissions in aspects of quality and specifications inform us of the model number and product number described on the identification plate The identification plate...

Страница 6: ...physical injury Avoid hitting the glass part of the display with tools This may damage the glass and result in physical injury Perform installation correctly Insufficient installation or no installati...

Страница 7: ...not leave the transmitter part uncovered for fear of sparks or ignition CAUTION This instrument is shipped under strict product control by Azbil Corporation Do not modify the instrument under any circ...

Страница 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...

Страница 9: ...at is set before main unit is fixed 1 16 Flange bolt tightening torque 1 16 Electrical wiring 1 18 Wiring for waterproof model 1 18 Wiring for explosion proof model 1 20 Chapter 2 Operation 2 1 Princi...

Страница 10: ...rting measurement 2 32 Display measured data 2 33 Liquid level input mm 2 33 Output being transmitted 2 33 Torque tube temperature C 2 33 Angle sensor temperature C 2 35 Input angle 2 36 Displaying an...

Страница 11: ...real level pinpoint adjustment 2 75 Damping adjustment 2 76 Zero span adjustment 2 76 Zero adjustment 2 77 Span adjustment 2 78 Operation sequence 2 79 Chapter 3 Maintenance 3 1 Daily maintenance item...

Страница 12: ...ment cycle 3 25 Replacement parts list 3 25 Table for selection of chamber bonnet gasket parts 3 26 Recommended replacement cycle 3 27 Replacing terminal block with indicator LCD 3 27 3 9 Starting ins...

Страница 13: ...Figure 1 24 Relationship between Supply Voltage and External Load Resistance 1 20 Figure 1 25 Locking of transmitter part Case 1 21 Figure 1 26 Cable gland 1 21 Figure 1 27 Overall view of cable glan...

Страница 14: ...tion standard product external type S B type T B type 1 12 Table 1 3 Tightening Torque 1 17 Table 1 4 Temperature level for Explosion proof 1 21 Table 2 1 Display during external adjustment switch ope...

Страница 15: ...justment switch Available only when built in indicator is mounted Transmitter position Left side Transmitter position Right side Figure 1 1 Main Unit Section T type S S type S B type Main unit externa...

Страница 16: ...n Azbil Corporation 1 2 Model SLX 110 120 Smart displacement type level transmitter T B T S S S S B Figure 1 3 Chamber Figure 1 4 Float Others accessories Figure 1 5 Float mounting tool Figure 1 6 Hex...

Страница 17: ...O mmAq inH2O gf cm2 kgf cm2 atm mbar bar psi mmHg inHg kgf cm2 G mbar G bar G m3 kgf cm2 abs mmHg abs inHg abs k m h l h k h Sk h t h m3 h km3 h Nm3 h kNm3 h min k min m3 min Nm min N min Nm3 min k D...

Страница 18: ...ry Perform installation correctly Insufficient installation or no installation may result in output errors or violate applicable regulations This product is heavy Pay attention to the scaffolding and...

Страница 19: ...e of target gas II CT3 IIC all gases vapor T3 gas vapor with ignition temperature exceeding 200 C II CT4 IIC all gases vapor T4 gas vapor with ignition temperature exceeding 135 C II CT5 IIC all gases...

Страница 20: ...odel number Unit seal inside transmitter part cover Bolt nut between chamber bonnet when with external type chamber is specified Gasket between chamber bonnet when external type chamber is specified T...

Страница 21: ...rt the assembly pin and adequately bend it using pliers so that the pin does not come out Checking specification Make sure the specifications on the identification plate conform to your requirements M...

Страница 22: ...tion Azbil Corporation 1 8 Model SLX 110 120 Smart displacement type level transmitter Store the product indoors at normal temperature normal humidity approximately 25 C 65 RH and free from vibration...

Страница 23: ...r preventing correct output from being obtained If viscosity of the liquid to be measured increases in the chamber due to a temperature drop or if heat loss becomes a problem it is recommended to keep...

Страница 24: ...transmitter part resulting in insufficient performance and early deterioration of component parts etc Extension Tramsmitter part No warmer available Figure 1 12 Applying heat installation Main unit f...

Страница 25: ...cement type level transmitter 1 11 In case of external type when float is set after main unit is fixed 1 Remove the blind flange Gasket Bonnet Blind flange Figure 1 13 Removing a bling flange Float ha...

Страница 26: ...able 1 2 Azbil Corporation standard product external type S B type T B type If the float drops into the lower section connection flange tilt the float so that it does not drop and carefully mount it o...

Страница 27: ...ter 1 13 2 Slowly lower the main unit from the upper section of the chamber and fix it to the flange using bolts and nuts Figure 1 15 Note Check that the gasket has been inserted Be careful not to ben...

Страница 28: ...18 Note If the bonnet interior is dark illuminate it with a flashlight Handle Insert into the float hanger hole Float hanger hole Float hanger Figure 1 16 Float mounting tool Figure 1 17 Float hanger...

Страница 29: ...l for mounting float Bonnet stopper Torque arm Hanger Cut image Figure 1 19 Mounting the float hanger Case 1 Hook the float hanger over the pin while moving it forward the torque tube housing directio...

Страница 30: ...nger over the pin of the torque arm inside the main unit Note The float hanger can be oriented in any direction Make sure the hanger is hooked over both sides of the pin 5 Slowly lower the main unit f...

Страница 31: ...type level transmitter 1 17 Table 1 3 Tightening Torque Flange position Bolt size Tightening torque N m Blind flange M14 127 20 Bonnet flange 3in CLASS 150 4in CLASS 150 M16 147 20 Bonnet 3in CLASS 30...

Страница 32: ...duit that is not used to prevent moisture or precipitation from entering CHK S S CHK M E M DISP FLOW UP ZERO DOWN SUPPLY S Terminal SUPPLY CHK S Terminal Load resistance more than 250 Ohms Supply volt...

Страница 33: ...ing terminal and the other on the transmitter part case external grounding terminal Ground either one Use a grounding terminal with a resistance to ground of 100 ohms or less or connect it to ground o...

Страница 34: ...rproof model and the following instructions See National Institute of Industrial Safety technical guideline Factory Explosion Proof Electrical Installation Guide for Users Gas Explosion Proof 1994 iss...

Страница 35: ...ct wiring M3 Cover locking screw Figure 1 25 Locking of transmitter part Case Draw the cable into this instrument using the provided pressure proof packing type cable adapter as shown in the figure be...

Страница 36: ...and improve the insulation performance and mechanical strength If it is necessary to change the orientation of the cable use a pressure proof elbow Structure of cable gland An overall view and explod...

Страница 37: ...ounting example Attach the cable gland and pressure proof elbow to the conduit coupling opening of the terminal box as shown in the figure below When only cable gland is used When cable gland and pres...

Страница 38: ...eference to the exploded view paying attention to their orientations WARNING The diameter of the cable and that of the packing may not match which may cause flames to flow out resulting in humidity in...

Страница 39: ...ure 1 31 Matching lock nut end face and O ring groove end face 2 Screw the pressure proof elbow into the conduit coupling opening of the transmitter part until the lock nut end face touches the end fa...

Страница 40: ...Installation Azbil Corporation 1 26 Model SLX 110 120 Smart displacement type level transmitter...

Страница 41: ...pended and transmitted to the torque tube The torque tube has a dual function as sealing of the process liquid and torsional spring and converts torque to an angle This angle is detected by an angle s...

Страница 42: ...Screw Angle sensor Built in Sensor housing Figure 2 1 Schematic Structural Drawing A D Float Torque tube Angle sensor Torque arm Knife edge Temperature sensor D A CPU Angle Torque Buoyancy Input Liqu...

Страница 43: ...arbitrary engineering unit values The digital display of this instrument uses a 4 5 digit 7 segment LCD as shown below and the following points should be noted DISP FLOW UP ZERO DOWN Figure 2 4 4 5 di...

Страница 44: ...s Blink ON In constant current mode the entire bar graph blinks When blinking the bar graph display and digital display blink alternately Display during external adjustment switch operation During an...

Страница 45: ...procedure Make sure the SFC is a SFC160 260 Ver 8 0 or newer 1 Turn on DC power 2 Check that the instrument LCD displays some data 3 Connect the SFC and check the specification see page 2 6 4 Print ou...

Страница 46: ...o connect the SFC communication cable and terminals of this instrument as follows Red wire Supply terminal Black wire Supply terminal CHK S S CHK M E M DISP FLOW UP ZERO DOWN SUPPLY S Terminal SUPPLY...

Страница 47: ...on condition Before starting communication with this instrument be sure to change the control loop of the process to manual control Step Button Procedure SFC screen 1 Turn on power to the SFC LOOP IN...

Страница 48: ...HIFT Press SHIFT SHIFT 3 P 9 PRINT Press 9 TAG NO WORKING 4 Printing starts PRINTING 5 CLR No When printing is completed the system is again on standby waiting for operation To stop printing press CLR...

Страница 49: ...Output mode analog DE Serial number S W version Damping time constant Span LRV URV Range Specific gravity specific gravity to be set in basic data setting Torque tube temperature coefficient COEF TQ s...

Страница 50: ...d tank can be changed up to upper limit Method using SFC Zero adjustment Carry out a zero adjustment with the liquid level in the chamber liquid tank set to 0 in the case of the level gauge the float...

Страница 51: ...n adjustment without changing specific gravity conventional water level adjustment by inputting the liquid level for which specific gravity is converted beforehand giving 100 equivalent buoyancy gener...

Страница 52: ...ENTER Yes NON VOL Press ENTER DATA CONFIG WORKING 9 CLR No Change of specific gravity has been completed press CLR once to return to the original condition DATA CONFIG DATA LOAD SLX CONFIG DATA CONFI...

Страница 53: ...pecific gravity set value water is displayed GRAVITY 1 0000 18 Enter the specific gravity of the fluid to be measured Example Enter value of 0 9 GRAVITY 0 9_ 19 ENTER Yes NON VOL Press ENTER GRAVITY E...

Страница 54: ...approximately 3 sec 2 When pUP ZERO appears turn OFF the switch This enters Damping adjustment mode UP ZERO 3 Turn the switch counterclockwise and display 199 9 below 0 4 ZERO appears after approxima...

Страница 55: ...stment mode UP ZERO 3 Turn the switch counterclockwise and display 199 9 below 0 4 ZERO appears after approximately 10 sec and Zero span adjustment mode is entered The current output value is displaye...

Страница 56: ...liquid level of the glass gauge Method using SFC Step Button Procedure SFC screen 1 OUT J PUT INPUT Press OUTPUT OUTPUT TAG 0001 WORKING 2 The current output value is displayed OUTPUT TAG 0001 40 0 3...

Страница 57: ...switch This enters Zero adjustment mode to adjust to real level ZERO DOWN 3 1 Hold the switch counterclockwise The readout reduces continuously When the desired readout appears turn OFF the switch Th...

Страница 58: ...l of the valve so that no drastic pressure liquid level changes including flashing occur Make sure there is no liquid or gas leakage from the coupling of the pressure container such as the chamber and...

Страница 59: ...ual CM2 SFC100 2001 The SFC that can be used with the SLX is SFC160 260 Ver 8 0 or newer WARNING Always the SFC is a non hazardous location otherwise an explosion can result from an electrical dischar...

Страница 60: ...on the screen press CLR No Answering No to a question on the screen using a dedicated function moves a step back to the layer at the previous level Answering No to Do you quit returns the screen to th...

Страница 61: ...S SFC A ID B CONF C DAMP D UNITS H NEXT G SET URV F 100 LRV E 0 MENU I ITEM OUT J PUT COR K RECT L PREV M N 7 O 8 P 9 Q R 4 S 5 T 6 X 3 W 2 V 1 U STAT Y SPAN Z 0 ALPHA SHIFT CLR No ENTER Yes DE READ D...

Страница 62: ...nter The letter entered appears Letters are marked on the top right corner of each key 3 To exit press ALPHA again ALPHA To input a numeral or symbol or use a different function use the following proc...

Страница 63: ...pes according to their functions to make it easier for you to find the necessary keys The color codes are as follows CAUTION There are also keys that will not be used for measurements using this instr...

Страница 64: ...en key is pressed after SHIFT A ID DE READ ID Starts communication with this instrument TAG NO of this instrument appears TAG NO can be changed in this screen Used when converted output is DE The func...

Страница 65: ...after SHIFT URV F 100 URV100 Displays the upper range value of the current setting range The upper range value can be changed in this screen No function MENU I ITEM DE CONF Menu This key by itself do...

Страница 66: ...atically set in combination with other functions No function H NEXT p Displays the next function in the same layer Pressing this key after DAMP sends a damping time constant next No function L PREV q...

Страница 67: ...n When the key alone is pressed When key is pressed after SHIFT ENTER Yes NON VOL ENTER Used to send data to this instrument Used to answer Yes to a question on the screen Non volatile data Writes set...

Страница 68: ...HIFT P 9 PRINT 9 Enters numeric 9 Data printing Prints out a list of internal data of this instrument This is called maintenance print valid only for SFC with a printer O 8 FEED 8 Enters numeric 8 Pap...

Страница 69: ...n TIME Enters After pressing ALPHA once enter Time Displays the current date and time valid only for SFC with a printer M Enters a decimal point g After pressing ALPHA once enter a space Memo Used to...

Страница 70: ...ing range Alphabetic characters are entered by pressing the desired letter after pressing the ALPHA key Display on key Description When the key alone is pressed When key is pressed after SHIFT U STAT...

Страница 71: ...sed When key is pressed after SHIFT M g Advances the cursor by one space No function Q A DE f Moves the cursor back by one space Output mode change Changes output mode from Analog to DE or DE to Analo...

Страница 72: ...ons that appear displayed on the screen Operation when starting measurement Step Button Procedure SFC screen 1 Turn on the power to the SFC LOOP IN MANUAL 2 ENTER Yes NON VOL Make sure that the contro...

Страница 73: ...INPUT TAG 0001 WORKING 3 Displays the current liquid level Updated approximately every 6 seconds INPUT TAG 0001 150 0 mm Output being transmitted Step Button Procedure SFC screen 1 OUT J PUT INPUT Pre...

Страница 74: ...EV press NEXT or PREV to go to the torque tube temperature reading screen SLX CONFIG TQTUBE TEMP 3 ENTER Yes NON VOL Press ENTER TQTUBE TEMP WORKING 4 CLR No Displays the current torque tube temperatu...

Страница 75: ...N CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the angle sensor temperature reading screen SLX CONFIG PTS TEMP 3 ENTER Yes NON VOL Press ENTER Communication commences SLX CONFIG WORKING 4 CLR...

Страница 76: ...re SFC screen 1 B CONF Press the CONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the sensor angle reading screen SLX CONFIG ENTERED DEG 3 ENTER Yes NON VOL Press ENTER S...

Страница 77: ...r row for 2 sec and the former value will remain current Numeric input Enter numeric values for the lower range value of the liquid level in millimeters Step Button Procedure SFC screen 1 LRV E 0 Pres...

Страница 78: ...rrent lower range value will appear LRV TAG 0001 0 1200 mm 2 G SET Press SET LRV TAG 0001 SET LRV 3 ENTER Yes NON VOL Press ENTER LRV TAG 0001 WORKING 4 The actual input level becomes the zero point S...

Страница 79: ...39 Step Button Procedure SFC screen 4 G SET Press SET OUTPUT TAG 0001 SET REQ LEVEL 5 Press ENTER OUTPUT TAG 0001 WORKING 6 ENTER Yes NON VOL A zero adjustment is performed so that the actually input...

Страница 80: ...s 0 4 times the range If a value beyond the allowable setting range is entered ENTRY SENS RNG will appear on the lower row for 2 sec and the former value will remain current Numeric input Enter the li...

Страница 81: ...ess URV The current upper range value will appear URV TAG 0001 300 1 mm 2 G SET Press SET URV TAG 0001 SET URV 3 ENTER Yes NON VOL Press ENTER URV TAG 0001 WORKING 4 The actual input level becomes the...

Страница 82: ...ravity Step Button Procedure SFC screen 1 B CONF Press CONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the basic data setting screen SLX CONFIG DATA CONFIG 3 ENTER Yes N...

Страница 83: ...oration Operation Model SLX 110 120 Smart displacement type level transmitter 2 43 Step Button Procedure SFC screen 8 ENTER Yes NON VOL Press ENTER DATA CONFIG WORKING 9 Setting completed DATA CONFIG...

Страница 84: ...Press CONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the basic data setting screen SLX CONFIG DATA CONFIG 3 ENTER Yes NON VOL Press ENTER SLX CONFIG WORKING 4 The curr...

Страница 85: ...FC screen 8 H NEXT or L PREV Press NEXT or PREV to go to the download selection screen DATA CONFIG DOWNLOAD DATA 9 ENTER Yes NON VOL Press ENTER DATA CONFIG WORKING 10 CLR No Setting completed Pressin...

Страница 86: ...L SHIFT Y SPAN URL Step Button Procedure SFC screen 1 B CONF Press CONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the SERIAL No screen SLX CONFIG SERIAL NO 3 ENTER Yes...

Страница 87: ...s NON VOL Press ENTER RANGE ENTERED IN SFC 10 H NEXT or L PREV Press NEXT or PREV to go to the download selection screen BASE CONFIG DOWNLOAD DATA 11 ENTER Yes NON VOL Press ENTER A confirmation scree...

Страница 88: ...cedure SFC screen 1 B CONF Press CONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the SERIAL No screen SLX CONFIG SERIAL NO 3 ENTER Yes NON VOL Press ENTER SLX CONFIG WOR...

Страница 89: ...er value of 0 547 OFFSET 0 547_ DEG 10 ENTER Yes NON VOL Press ENTER OFFSET ENTERED IN SFC 11 H NEXT or L PREV Press NEXT or PREV to go to the download selection screen BASE CONFIG DOWNLOAD DATA 12 EN...

Страница 90: ...ONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV Press NEXT or PREV to go to the SERIAL No screen SLX CONFIG SERIAL NO 3 ENTER Yes NON VOL Press ENTER SLX CONFIG WORKING 4 The serial number will appe...

Страница 91: ...s Example Enter value of 1 4 COEF MT 1 4_ 10 ENTER Yes NON VOL Press ENTER COEF TQ ENTERED IN SFC 11 H NEXT or L PREV Press NEXT or PREV to go to the download selection screen BASE CONFIG DOWNLOAD DAT...

Страница 92: ...AMP Press DAMP The current damping time constant value will appear DAMP TAG 0001 0 0 s 2 H NEXT or L PREV Press NEXT or PREV to select the desired damping time constant DAMP TAG 0001 WORKING 3 The dam...

Страница 93: ...printer which prints 24 characters per line When the power of the SFC is turned on the print head makes a to and fro movement once and stops and then the printer is on stand by At this time the recor...

Страница 94: ...ecord such things as the setting condition and fault condition of this instrument Procedure Maintenance printout is performed using the following procedure This operation can also be performed during...

Страница 95: ...e printed as SLX Output mode analog DE Serial number S W version Damping time constant Span LRV URV Range Specific gravity specific gravity to be set in basic data setting Torque tube temperature coef...

Страница 96: ...Procedure SFC screen 1 CLR No press CLR until the screen to the right appears SLX TAG 0001 READY 2 SHIFT Press SHIFT and 0 in that order SHIFT SLX TAG 0001 ACTION PRINT 3 ENTER Yes NON VOL Press ENTER...

Страница 97: ...001 READY Example of action printout A printout example which corresponds to key operations is shown below Z 0 ACT PR SHIFT ENTER Yes NON VOL keys 0 SHIFT CLR No keys C DAMP keys ACTIONPRINT START TAG...

Страница 98: ...nsmitter Display and change of setting of this instrument Changeable and non changeable data a Changeable Not changeable Item Display Change Tag No a a Serial number a Software version a Indicator dis...

Страница 99: ...plate of this instrument Here a case where the tag No is to be changed to TAG 0001 is given Step Button Procedure SFC screen 1 ALPHA T 6 A ID DE READ G SET Press ALPHA 6 ID and SET in that order SLX...

Страница 100: ...creen 1 B CONF Press CONF SLX CONFIG FUNCTION CONFIG 2 H NEXT or L PREV press NEXT or PREV to go to the SERIAL No screen SLX CONFIG SERIAL NO 3 ENTER Yes NON VOL Press ENTER SLX CONFIG WORKING 4 CLR N...

Страница 101: ...is instrument can be displayed using the SFC Use the following procedure to display the software versions SFC 8 0 This instrument 3 0 Step Button Procedure SFC screen 1 SHIFT Press SHIFT SHIFT 2 X 3 S...

Страница 102: ...isplay format appears Example PV value DISPLAY TYPE 0 0 4 MENU I ITEM DE CONF Press MENU and select a display format Example engineering unit value real scale DISPLAY TYPE ENG UNIT 4 5 DIG 5 H NEXT or...

Страница 103: ...TEM DE CONF Press MENU and select a display format DISPLAY TYPE ENG UNIT 4 5 DIG 5 ENTER Yes NON VOL Press ENTER DISPLAY TYPE WORKING 6 1 The current engineering unit value real scale will appear EULO...

Страница 104: ...V press NEXT or PREV to go to the download selection screen DISPLAY TYPE DOWNLOAD DATA 10 ENTER Yes NON VOL Press ENTER DISPLAY TYPE WORKING 11 CLR No Setting completed It takes approximately 6 sec un...

Страница 105: ...ery from the fault condition a normal value is output automatically With the SLX it is not possible to confirm the burnout direction using SHIFT STAT DOWN SCALE appears but this display content has no...

Страница 106: ...press NEXT or PREV to go to the download selection screen FAILSAFE DOWNLOAD DATA 7 ENTER Yes NON VOL Press ENTER FUNCTION CONFIG WORKING 8 CLR No Setting completed It takes approximately 6 sec until...

Страница 107: ...e three types of setting are available necessary according to operations carried out by means of communication Output signal mode setting Select the type of data to be output from three of the followi...

Страница 108: ...ep Button Procedure SFC screen 1 OUT J PUT INPUT Press OUTPUT OUTPUT TAG 0001 WORKING 2 The current output data will appear Example 65 2 OUTPUT TAG 0001 65 20 3 Enter 50 using numeric keys OUTPUT TAG...

Страница 109: ...The system has recovered from the constant current source mode The disappears SLX TAG 0001 READY Memo recording The function of recording a memo in the SFC is called a scratch pad There are scratch pa...

Страница 110: ...ion 2 70 Model SLX 110 120 Smart displacement type level transmitter Step Button Procedure SFC screen 2 Z 0 ACT PR V 1 TIME N 7 Press 0 1 and 7 in that order MEMO 1 01 7 3 ALPHA M Press ALPHA and g in...

Страница 111: ...R URV F 100 R 4 O 8 FEED M C DAMP H NEXT LRV E 0 C DAMP COR K RECT RESET Press 0 URV 4 8 g DAMP NEXT LRV DAMP and CORRECT in that order MEMO 1 01 7 ZERO CHECK 5 ENTER Yes NON VOL Press ENTER The writi...

Страница 112: ...SSCR PADS 3 The writing method is the same as that of scratch pad 1 4 CLR No To exit scratch pad 2 press CLR SLX TAG 0001 READY Charging SFC If appears blinking in the center of the upper row on the S...

Страница 113: ...ocedure 1 Turn OFF the power to the SFC 2 Disconnect the communication cable on the transmitter side 3 Pull out the SFC plug of the communication cable 4 Connect the plug of the battery charger cable...

Страница 114: ...reflected in the output after the normal condition is recovered from the adjustment mode Do not use a magnetic driver because this may prevent accurate adjustment In the case of an engineering unit r...

Страница 115: ...LCD screen 1 Hold the switch counterclockwise for approximately 3 sec 2 When ZERO DOWNq appears on the display turn switch OFF This means that the Zero adjustment mode to adjust to real level has been...

Страница 116: ...counterclockwise one turn the damping time constant decreases by an increment of 1 The normal condition is restored after approximately 10 sec UP ZERO 3 2 Every time the switch is turned clockwise on...

Страница 117: ...nt mode has been activated UP ZERO 3 Turn the switch counterclockwise and 199 9 below 0 will appear 4 ZERO appears after approximately 10 sec and Zero span adjustment mode is activated The current out...

Страница 118: ...stment mode has been acticated UP ZERO 3 Turn the switch counterclockwise 199 9 below 0 will appear 4 ZERO appears after approximately 10 sec and Zero span adjustment mode is activated The current out...

Страница 119: ...pproximately 10 sec Zero adjustment mode pinpoint adjustment to adjust to real level Reverts to normal condition in approximately 10 sec ZERO DOWN ZERO DOWN ZERO DOWN UP ZERO UP ZERO UP ZERO Zero span...

Страница 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...

Страница 121: ...tools This may damage the glass and result in physical injury Perform installation correctly Insufficient installation or no installation may result in output errors or violate applicable regulations...

Страница 122: ...Disassembly and cleaning of wetted parts If rated accuracy is not achieved by a test as described in 1 above or if the measured fluid is of high viscosity adhesive or extremely corrosive disassemble...

Страница 123: ...of torque arm contact surface too short they may contact before liquid level becomes zero resulting in unsatisfactory accuracy linearity Float Remove deposit from the surface of float if any Note If...

Страница 124: ...nce exercise care in loss or dropping of these parts Disassembly of main body torque arm bonnet and torque tube housing assembly Remove blind flange on the side of bonnet Loosen torque arm mounting sc...

Страница 125: ...sing and torque tube WARNING Steam detergent or deposit which has been injected into inside of torque tube housing will flow out through the gap between torque tube housing and torque tube because the...

Страница 126: ...hand or left hand orientation of instrument head cannot be reversed on SLX The orientation has been set at the time of factory shipment Under no circumstance torque tube housing should be mounted on t...

Страница 127: ...acement type level transmitter 3 7 Zero and span adjustment Calibrate in installed position on process equipment with water filled Refer to Zero span adjustment on page 2 10 Or calibrate with weight R...

Страница 128: ...peratures torque tube temperature coefficients parameters to compensate for measuring errors which are satiable by means of SFC communication are provided If an appropriate torque tube temperature coe...

Страница 129: ...Torque tube temperature coefficient to be changed Current torque tube temperature coefficient Material coefficient Input angle Torque tube temperature C Angle sensor temperature C Read from the SFC pr...

Страница 130: ...specific gravity set value will appear Example 0 8 GRAVITY 0 800 5 H NEXT or L PREV Press NEXT or PREV to go to the coefficient setting screen Example 0 COEF TQ 0 000 6 Enter the desired torque tube...

Страница 131: ...ue tube temperature coefficient is assumed to be COEF TQ 1 3 then the amount of output shift is 1 5 per a variation of 55 C Furthermore in a case the instrument is used as an interface gauge and a hea...

Страница 132: ...le Out put Liquid level 0 equivalent state 30mm 0mm 300mm 1 6DEG 0 85DEG 1 685DEG 10 State after LRV adjustment 30mm 30mm 270mm 1 6DEG 0 85DEG 1 685DEG 0 Calibration key sequence CORRECT ENTER This ad...

Страница 133: ...include pans for weights etc According to the level gauge weight 1 weight 2 is 0 calibrated load and weight 1 is 100 calibrated load According to the interface gauge weight 3 weight 4 is 0 calibrated...

Страница 134: ...ty of upper layer liquid g cm3 r2 Specific gravity of lower layer liquid g cm3 r2 r1 Other parameters are same to a liquid gauge 3 Turn the power to the instrument ON and connect the SFC See 2 3 Items...

Страница 135: ...mm 6 COR K RECT RESET Press CORRECT LRV TAG 0001 ZERO INPUT 7 ENTER Yes NON VOL Press ENTER A confirmation screen will appear LRV TAG 0001 ARE YOU SURE 8 ENTER Yes NON VOL After checking that the weig...

Страница 136: ...Press ENTER URV TAG 0001 WORKING 5 The URV is set to 300 mm URV TAG 0001 300 0 mm 6 COR K RECT RESET Press CORRECT URV TAG 0001 CORRECT LRV 7 ENTER Yes NON VOL Press ENTER A confirmation screen will a...

Страница 137: ...If calibration is unavoidable the following instruments are required Instruments used Precision ammeter with a precision of 0 03 FS or higher Precision resistor 250W 0 005 SFC Setup While referring t...

Страница 138: ...f 0 OUTPUT TAG 0001 0 3 ENTER Yes NON VOL Press ENTER This sets the instrument to a 4 mA 0 constant current source mode Once the constant current source mode is activated a appears on the screen OUTPU...

Страница 139: ...UTPUT TAG 0001 WORKING OUTPUT TAG 0001 INCREASED 4mA OUTPUT TAG 0001 CORRECT DAC ZERO 8 L PREV Press PREV Check the reading of the ammeter while pressing this key OUTPUT TAG 0001 WORKING i OUTPUT TAG...

Страница 140: ...UT J PUT INPUT Press OUTPUT OUTPUT TAG 0001 WORKING i OUTPUT TAG 0001 0 00 2 V 1 Z 0 ACT PR Z 0 ACT PR Press numeric keys 1 0 0 in that order OUTPUT TAG 0001 100 3 ENTER Yes NON VOL Press ENTER This s...

Страница 141: ...T DAC SPAN 7 H NEXT Press NEXT Check the reading of the ammeter while pressing this key OUTPUT TAG 0001 WORKING OUTPUT TAG 0001 INCREASED 20mA OUTPUT TAG 0001 INCREASED 4mA 8 L PREV Press PREV Check t...

Страница 142: ...nd cancel the constant current source mode Step Button Procedure SFC screen 1 SHIFT Press SHIFT SHIFT 2 ENTER Yes NON VOL Press ENTER Forced data writing is completed SLX TAG NO WORKING i SLX TAG 0001...

Страница 143: ...o record or print out the currently set data Step Button Procedure SFC screen 1 SHIFT Press SHIFT SHIFT 2 COR K RECT RESET Press CORRECT SLX TAG 0001 RESET CORRECTS 3 ENTER Yes NON VOL Press ENTER A c...

Страница 144: ...he instrument 2 Short between and SUPPLY terminals and between and METER terminals The product is shipped with these METER terminals shorted 3 Conduct tests between the shorted SUPPLY terminals and th...

Страница 145: ...g 80277119 001 1 1 Cover no window anti corrosion finish O ring 80277119 002 1 1 Cover no window anti severe corrosion finish O ring 80277119 003 1 1 5 Pressure proof packing type cable adapter 803439...

Страница 146: ...72 113 i i i i 2 3 4 C D E F H J K 1 80353472 114 SLX120 Except 20 1 2 3 4 1 2 U M A E 1 A B G 1 80353472 005 i i i i i 2 3 C D H 1 80353472 006 i 20 i i i 1 A B G 1 80353472 003 i i i i i 2 3 C D H 1...

Страница 147: ...Average ambient temperature Replacement cycle 30 C or below 10 years 30 C to 40 C 5 years 40 C to 50 C 2 years Replacing terminal block with indicator LCD This section describes the replacement proced...

Страница 148: ...emove the three screws that fix the terminal block Fixing screw Fixing screw l Draw the terminal block toward you remove the two connectors and separate the terminal block from the instrument Connecto...

Страница 149: ...oard o Assemble the terminal block into the instrument in the reverse order If the terminal block is assembled into the case turn the terminal block so that the lead wires are not caught and bind the...

Страница 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...

Страница 151: ...g to the work procedure specified in the explosion proof guideline CAUTION After installation do not use this instrument as a foothold etc This may damage the instrument or may result in physical inju...

Страница 152: ...ropriate action according to this self diagnostic message Operation check When checking the operation of this instrument connect the SFC to this instrument and confirm that the instrument is communica...

Страница 153: ...DIR In this case the operations of ID OUTPUT and STAT are active A ID DE READ OUT J PUT INPUT U STAT F S DIR After taking action press STAT and make sure Self diagnostic result OK appears U STAT F S...

Страница 154: ...le in the operation of the SLX and may damage the SLX itself if left unattended The output continues in the set burnout direction The output is set to the burnout direction lower range value at the ti...

Страница 155: ...C SLX TAG 0001 PTST OVER TEMP The angle sensor temperature exceeds the allowable temperature range Adjust the angle sensor temperature to a range of 30 to 80 C in the case of specification with explos...

Страница 156: ...the SFC and transmitter wiring and power supply SLX TAG 0001 PRINTER FAIL Printer operation impossible Contact Azbil Corporation SLX TAG 0001 LOW LOOP RES Insufficient loop resistance Check the resis...

Страница 157: ...RV Is the input value appropriate for the value to be set Check the input value If wrong correct it ENTRY SENS RNG When the set value exceeds the allowable setting range of this instrument Press CLR c...

Страница 158: ...e digital display section according to the diagnostic content Self diagnostics upon power up Message Meaning Action Blinking Digital indicator RAM failure Replace the terminal block with an indicator...

Страница 159: ...Azbil Corporation Repair Model SLX 110 120 Smart displacement type level transmitter 4 9 Message Meaning Action o Displayed alternately Fault of this instrument or indicator Contact Azbil Corporation...

Страница 160: ...l Corporation 4 10 Model SLX 110 120 Smart displacement type level transmitter 4 3 Removal installation method For the method of removal or reinstallation of the main unit see 1 6 Installation method...

Страница 161: ...on to preventing corrosion deformation damage etc with respect to the products case cover and the like When installing operating and maintaining the product be sure to read this manual In addition obs...

Страница 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...

Страница 163: ......