Operation
Azbil Corporation
2-68
Model SLX 110/120 - Smart displacement type level transmitter
Constant current source mode
Constant current source mode setting
Example: When output is fixed to 50% (12 mA)
Step
Button
Procedure
SFC screen
1
OUT- J
PUT
INPUT
Press [OUTPUT].
OUTPUT TAG-0001
WORKING...
2
The current output data will appear.
Example: 65.2%
OUTPUT TAG-0001
65.20 %
3
Enter 50% using numeric keys.
OUTPUT TAG-0001
50_ %
4
ENTER
( Yes )
NON-VOL
Press [ENTER].
OUTPUT TAG-0001
WORKING...
5
The 50% constant current source mode
is set. A “#” will appear. 12 mA is
output and the indicator display starts
to blink.
OUTPUT TAG-0001
50_ % #