Operation
Azbil Corporation
2-48
Model SLX 110/120 - Smart displacement type level transmitter
Offset angle
This is normally not required to be changed. (However, be sure to set the offset angle
when replacing the transmitter part.)
Step
Button
Procedure
SFC screen
1
B
CONF
Press [CONF].
SLX CONFIG
FUNCTION CONFIG ?
2
H
NEXT
or
L
PREV
Press [NEXT] or [PREV] to go to the
SERIAL No. screen.
SLX CONFIG
SERIAL NO. ?
3
ENTER
( Yes )
NON-VOL
Press [ENTER].
SLX CONFIG
WORKING...
4
The serial number will appear.
SERIAL NO.
0105010137
5
H
NEXT
or
L
PREV
press [NEXT] or [PREV] to go to the
standard setting screen.
BASE CONFIG ?
6
ENTER
( Yes )
NON-VOL
Press [ENTER].
BASE CONFIG ?
WORKING...
7
The current range will appear.
RANGE