Operation
Azbil Corporation
2-52
Model SLX 110/120 - Smart displacement type level transmitter
Damping time constant
Step
Button
Procedure
SFC screen
1
C
DAMP
Press [DAMP]. The current damping
time constant value will appear.
DAMP TAG - 0001
0.0 s
2
H
NEXT
or
L
PREV
Press [NEXT] or [PREV] to select the
desired damping time constant.
DAMP TAG - 0001
WORKING...
3
The damping time constant is changed.
Setting completed.
DAMP TAG - 0001
5.0 s
Allowable damping time constants (sec.): 0, 0.5, 1, 2, 3, 4, 5, 10, 50, 100
Factory setting: 2.0 s