Operation
Model SLX 110/120 - Smart displacement type level transmitter 2-41
Actual level input
Enter the actuall level while the liquid level is 100% equivalent.
Step
Button
Procedure
SFC screen
1
URV F
100%
Press [URV]. The current upper range
value will appear.
URV TAG - 0001
300.1 mm
2
G
SET
Press [SET].
URV TAG - 0001
SET URV
3
ENTER
( Yes )
NON-VOL
Press [ENTER].
URV TAG - 0001
WORKING...
4
The actual input level becomes the
upper range value. Setting completed.
URV TAG - 0001
299.8 mm
Span
This is a value of URV-LRV.
The span is for reference only and cannot be changed.
Step
Button
Procedure
SFC screen
1
Y
SPAN
URL
Press [SPAN].
SPAN TAG - 0001
300.2 mm
Содержание SLX 110
Страница 1: ...Smart Displacement type Level Transmitter Model SLX 110 120 User s Manual CM2 SLX100 2001...
Страница 4: ......
Страница 8: ...iv Model SLX 110 120 Smart displacement type level transmitter...
Страница 40: ...Installation Azbil Corporation 1 26 Model SLX 110 120 Smart displacement type level transmitter...
Страница 120: ...Operation Azbil Corporation 2 80 Model SLX 110 120 Smart displacement type level transmitter...
Страница 150: ...Maintenance Azbil Corporation 3 30 Model SLX 110 120 Smart displacement type level transmitter...
Страница 162: ...Azbil Corporation 5 2 Model SLX 110 120 Smart displacement type level transmitter...
Страница 163: ......
Страница 166: ......
Страница 168: ......