7-22
7-2-6. Contact output setting
High alarm value setting
To set the high alarm value of contact output, proceeds as follows:
1. From online menu,
Select:
1. Device setup
4. Detailed setup
2. Conf output
4. Digital output
1. Hi alarm
Fig. 7-38. will then be displayed.
Fig. 7-38.
2. Use the numeric keys to enter a high alarm value in the value input display.
Setting range of high alarm value is 0% to +115%. Do not set the value to be High alarm
value < Low alarm value.
3. Once a new value is entered, press F4 (ENTER) to return to the Digital output menu.
When the value is outside the range, error will be displayed. Input the value again.
4. After returning to the Digital output menu, press F2 (SEND). Changed setting will be
transmitted to the converter. The HART communicator mark will appear on the upper
right hand corner while HART is communicating with the device. The mark will
disappear once communication has properly completed.