5-27
Electrode status diagnostic flow chart
Install the MTG 2 to the pipe. Pipe should be empty
Electrode Status Diagnostic function
Default setting: SENSITIVITY OFF
Change the SENSITIVITY to HIGH
when the pipe is empty or the scale appears on electrode.
Electrode Status Diagnostic function is not applicable.
Change the SENSITIVITY to OFF.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
Blink
"EMPTY OR SCALE
ON ELECTRODE"
Change the SENSITIVITY to
HIGH when the flowtube is
filled with the process fluid.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
Use the Electrode Status
Diagnostic function with the
SENSITIVITY HIGH.
Change the SENSITIVITY to
MID when the flowtube is filled
with the process fluid.
Use the Electrode Status
Diagnostic function with the
SENSITIVITY MID.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
Change the SENSITIVITY to LOW
when the pipe is empty or the scale
appears on electrode.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
Change the SENSITIVITY to LL
when the pipe is empty or the scale
appears on electrode.
Electrode Status Diagnostic
function is not applicable.
Change the SENSITIVITY
to OFF.
Electrode Status Diagnostic
function is not applicable.
Change the SENSITIVITY
to OFF.
Change the SENSITIVITY to MID
when the pipe is empty or the scale appears on electrode.
NO
YES
NO
NO
YES
NO
YES
YES
NO
YES
Blink
"EMPTY OR SCALE
ON ELECTRODE"
NO
YES
Change the SENSITIVITY
to LOW when the flowtube is
filled with the process fluid.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
NO
YES
Electrode Status Diagnostic
function is not applicable.
Change the SENSITIVITY
to OFF.
Use the Electrode Status
Diagnostic function with the
SENSITIVITY LOW.
Change the SENSITIVITY to LLL
when the pipe is empty or the scale
appears on electrode.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
NO
YES
Change the SENSITIVITY to
LL when the flowtube is filled
with the process fluid.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
YES
NO
Electrode Status Diagnostic
function is not applicable.
Change the SENSITIVITY
to OFF.
Blink
"EMPTY OR SCALE
ON ELECTRODE"
NO
YES
Electrode Status Diagnostic
function is not applicable.
Change the SENSITIVITY
to OFF.
Use the Electrode Status
Diagnostic function with the
SENSITIVITY LL.
Set the SENSITIVITY as
LLL when the flowtube is
filled with the process fluid.
Use the Electrode Status
Diagnostic function with the
SENSITIVITY LLL.
Содержание MagneW Two-wire PLUS+ MTG15A
Страница 8: ...vi...
Страница 22: ...1 14...
Страница 56: ...2 34...
Страница 60: ...3 4 Fig 3 2...
Страница 66: ...3 10...
Страница 70: ...4 4...
Страница 144: ...5 74...
Страница 226: ...6 82...
Страница 268: ...7 42...
Страница 274: ...8 6...
Страница 275: ......
Страница 278: ......
Страница 280: ......