6-70
Resetting the internal data to factory setting (default) [SHIP DATA
RECOV] function
By executing shipping data recovery, you can reset the two wired magnetic flowmeter to the
default factory setting. (Please note that all the data will be reset when executing the [SHIP
DATA RECOV] function.) Use the following procedure to execute the shipping data recovery.
Step
Key
Procedure
SFC screen
1
CLR
( No )
Confirm that the SFC is set to “READY”.
If it is not, press the
CLR
( No )
key to set it
to “READY”.
SFCM00006009D
2
B
CONF
H
NEXT
or
L
PREV
Press the
B
CONF
key to access the
CONFIG functions. Press the
H
NEXT
key or
L
PREV
key to display the screen
as shown on the right.
SFCM00006020D
SFCM00006108D
3
ENTER
( Yes )
NON-VOL
H
NEXT
or
L
PREV
Press the
ENTER
( Yes )
NON-VOL
key. Press the
H
NEXT
key or
L
PREV
key to display the screen
as shown on the right.
SFCM00006130D
4
ENTER
( Yes )
NON-VOL
For [SHIPPING DATA RECOVERY],
press the
ENTER
( Yes )
NON-VOL
key. Shipping data
recovery function starts.
SFCM00006131D
SFCM00006132D
5
When shipping data recovery completes,
the display as shown on the right
appears.
SFCM00006133D
6
CLR
( No )
Press the
CLR
( No )
key and the screen
returns to the screen as in step 1.
SFCM00006009D
Содержание MagneW Two-wire PLUS+ MTG15A
Страница 8: ...vi...
Страница 22: ...1 14...
Страница 56: ...2 34...
Страница 60: ...3 4 Fig 3 2...
Страница 66: ...3 10...
Страница 70: ...4 4...
Страница 144: ...5 74...
Страница 226: ...6 82...
Страница 268: ...7 42...
Страница 274: ...8 6...
Страница 275: ......
Страница 278: ......
Страница 280: ......