6-74
Setting pulse scale and pulse scale unit [PULSE CONFIGURE] function
Use the following procedure to set the pulse scale and the pulse scale unit using SFC.
However, set the span frequency range: 0.001 Hz to 200 Hz. (Span frequency is a pulse
frequency when the maximum range (100%) of flow rate flows.)
Step
Key
Procedure
SFC screen
1
CLR
( No )
Confirm that the SFC is set to “READY”.
If it is not, press the
CLR
( No )
key to set it
to “READY”.
SFCM00006009D
2
B
CONF
H
NEXT
or
L
PREV
Press the
B
CONF
key to access the
CONFIG functions. Press the
H
NEXT
key or
L
PREV
key to display the screen
as shown on the right.
SFCM00006136D
SFCM00006020D
3
ENTER
( Yes )
NON-VOL
H
NEXT
or
L
PREV
Press the
ENTER
( Yes )
NON-VOL
key to access the
TOTALIZER functions. Press the
H
NEXT
key or
L
PREV
key to display
the screen as shown on the right.
SFCM00006142D
4
ENTER
( Yes )
NON-VOL
H
NEXT
or
L
PREV
Press the
ENTER
( Yes )
NON-VOL
key to enter into
PULSE setting function and press the
H
NEXT
key or
L
PREV
key to display
the screen as shown on the right.
Displays the actual pulse scale unit.
SFCM00006143D
5
MENU I
ITEM
DE CONF.
Press the
MENU I
ITEM
DE CONF.
key and select the unit
to be set. Available units are in the actual
unit system.
SFCM00006144D
Содержание MagneW Two-wire PLUS+ MTG15A
Страница 8: ...vi...
Страница 22: ...1 14...
Страница 56: ...2 34...
Страница 60: ...3 4 Fig 3 2...
Страница 66: ...3 10...
Страница 70: ...4 4...
Страница 144: ...5 74...
Страница 226: ...6 82...
Страница 268: ...7 42...
Страница 274: ...8 6...
Страница 275: ......
Страница 278: ......
Страница 280: ......