Criteria (2) for installation location
Installed position
Install the instrument at a place where the measured fluid always fills inside the detector. An
example of installation is shown in the figure below to illustrate this condition.
The fluid
may not fill
completely.
The fluid
may not fill
completely.
Prone to stagnation of air
Pump
Good
Good
Fig. 2-1. Example of installation
Note) Install the instrument under the condition marked by a circle in the figure above with the
detector filled with the fluid in full. If the detector is not filled in full, output errors may
result. If empty, output fluctuations may result.
If the measured fluid is highly viscous, we recommend installing the instrument on a
vertical pipe and flowing the fluid to ensure an axially symmetrical flow.
Arrange a straight pipe section upstream and downstream of the installed place. For the
straight section length, see the figure below.
Diverging pipe section
with a cone angle of 15
degrees or over
(Less than 15
degrees can
be deemed to be a
straight section.)
90-degree bend
Detector
Detector
Detector
Detector
Detector
Detector
5D or over
5D or over
5D or over
10D or over
10D or over
10D or over
5D or over
Pump of various types
T
Gate valve fully open
Valve of various types
Converging pipe section
(can be
deemed
as a straight
section.)
Upstream
Fig. 2-2. Straight pipe section upstream of detector (D: Nominal detector bore diameter)
Содержание MagneW Two-wire PLUS+ MTG15A
Страница 8: ...vi...
Страница 22: ...1 14...
Страница 56: ...2 34...
Страница 60: ...3 4 Fig 3 2...
Страница 66: ...3 10...
Страница 70: ...4 4...
Страница 144: ...5 74...
Страница 226: ...6 82...
Страница 268: ...7 42...
Страница 274: ...8 6...
Страница 275: ......
Страница 278: ......
Страница 280: ......