6-38
Printing example
The following shows an example of an actual configuration printout accompanied by line-by-
line descriptions.
Printing example
Meaning
‘02-01-01 00:00
Time when printed
TAG No. XXXXXXXX
Tag no.
Detector
Detector information
DIA
: 50 A
Diameter
TYPE
: MGG
Type
EX
: 300.0 mA
Detector constant
RANGE
: SINGLE
Range
ANA/DE : ANALOG XMTR
Communication mode
D1
: D1 NOT USED
Setting of contact input
DO
: DO NOT USED
Setting of contact output
SW VER
: 3.1
Software version
DAMP
: 3.00
Damping constant
SPAN1
: 70.69 m
3
Span
GRAVITY : 1.0000
Specific gravity
COEFF
: 1.0000
Correction coefficient
LOFCUT : ON 0.6 %
Low flow cutoff
F/S I
: UP
Burnout (4-20 mA output)
DO
: OPEN
Burnout (Contact output)
P
: HOLD
Burnout (Pulse output)
PULSE
Pulse information
CONF
: ADD
Setting of built-in counter
RESET
: 0000000000
Reset value
WEIGHT : 110 cc/p
Pulse scale
WIDTH
: DUTY 50%
Pulse width
DROP
: 0.5%
Dropout value
INPUT
: 70.69 m
3
Input value
OUTPUT : 100.02 %
Output value
STATUS CHECK= OK
Status