UMAX130511 Version 1.00A Preliminary Documentation
– May be subject to change
82 - 141
Sub-Index
1h to 2h (x = 1 to 2)
Description
AOx Output Scaling 2 PV
Access
RW
PDO Mapping
No
Value Range
Default Value
5000 [mV]
2.3.26. Object 7323h: AO Output Scaling 2 FV
This object defines the output field value when the input data is at or above the AO Output Scaling 2 PV value
as shown in Figure 11. It will be scaled in the physical unit of the output, dependent on type, with the resolution
defined in object 6332h AO Decimal Digits FV. The value can be set anywhere within the allowable output
range as outlined in Table 15.. This value can be set lower than object 7321h AO Output Scaling 1 FV for an
inverse response (i.e. decreasing) to an increasing input.
Object Description
Index
7323h
Name
AO Output Scaling 2 FV
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
2
Default Value
2
Sub-Index
1h to 2h (x = 1 to 2)
Description
AOx Output Scaling 2 FV
Access
RW
PDO Mapping
No
Value Range
Dependent on type (seeTable 17)
Default Value
5000 [mV] (see Table 16)
2.3.27. Object 7330h: AO Output Field Value
This object represents the target output drive field value as a result of the output logic described in Section
1.4, and the scaling applied as shown in Figure 11. It is defined in the physical unit of the output dependent
on type, as outlined in Table 16. The resolution of the object is defined in object 6332h AO Decimal Digits FV.
Object Description
Index
7330h
Name
AO Output Field Value
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h