This object specifies the type of analog output, as defined in Table 14.
Object Description
Index
6310h
Name
AO Output Type
Object Type
ARRAY
Data Type
UNSIGNED16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
2
Default Value
2
Sub-Index
1h to 2h (x = 1 to 2)
Description
AOx Output Type
Access
RW
PDO Mapping
No
Value Range
Default Value
10 (voltage)
2.3.23. Object 7320h: AO Output Scaling 1 PV
This object defines the minimum value of the input, and should be specified to equal the corresponding scaling
object of the control source, as outlined in Table 17. It will be scaled in the physical unit of the control source.
The resolution will ALWAYS be dependent on object 6302h AO Decimal Digits PV, even when the output is
not being controlled directly by the AO Output PV object 7300h. This object must always be smaller than
object 7322h AO Output Scaling 2 PV.
Object Description
Index
7320h
Name
AO Output Scaling 1 PV
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
2
Default Value
2
Sub-Index
1h to 2h (x = 1 to 2)
Description
AOx Output Scaling 1 PV
Access
RW
PDO Mapping
No
Value Range
Default Value
0 [mV]