UMAX130511 Version 1.00A Preliminary Documentation
– May be subject to change
134 - 141
Data Type
UNSIGNED16
Entry Description
Subindex
0h
Description
Number of entries
Access
RO
PDO Mapping
No
Value Range
3
Default Value
3
Sub-index
1h
Description
FD1 Set Threshold
Access
RW
PDO Mapping
No
Value Range
5042h at sub-index 1 to 1250 [ºC x 10]
Default Value
1100 (110.0ºC)
Sub-index
2h
Description
FD2 Set Threshold
Access
RW
PDO Mapping
No
Value Range
5042h at sub-index 2 to 1000 [V x 10]
Default Value
500 (50.0V)
Sub-index
3h
Description
FD3 Set Threshold
Access
RW
PDO Mapping
No
Value Range
80 to 5042h at sub-index 3 [V x 10]
Default Value
90 (9.0V)
2.4.84. Object 5042h: FD Clear Threshold
This object sets the value that will clear a fault detection error in the 2IN-2OUT-SIG-CO if the measured field
value (5040h) goes below (FD 1 and FD 2) or above (FD 3) this threshold. This value must be in the same
units as the field value for the fault, as determined by the sub-index.
Object Description
Index
5042h
Name
FD Clear Threshold
Object Type
ARRAY
Data Type
UNSIGNED16
Entry Description
Subindex
0h
Description
Number of entries
Access
RO
PDO Mapping
No
Value Range
3
Default Value
3