UMAX130511 Version 1.00A Preliminary Documentation
– May be subject to change
84 - 141
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
2
Default Value
2
Sub-Index
1h to 2h (x = 1 to 2)
Description
AOx Fault Mode
Access
RW
PDO Mapping
No
Value Range
Default Value
1 (apply pre-defined FV)
2.3.30. Object 7341h: AO Fault Field Value
This object contains the pre-defined field value of an analog output when a fault condition is present, and the
corresponding sub-index in object 7341h is enabled. It will be scaled in the physical unit of the output,
dependent on type, with the resolution defined in object 6332h AO Decimal Digits FV.
Object Description
Index
7341h
Name
AO Fault Field Value
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
2
Default Value
2
Sub-Index
1h to 2h (x = 1 to 2)
Description
AOx Fault Field Value
Access
RW
PDO Mapping
No
Value Range
Dependent on type and range (see Table
16)
Default Value
500 [mV]
2.3.31. Object 7450h: PID Proportional Band
This object describes the proportional band gain (G in Figure 14) of the PID algorithm. The value is always
interpreted as having a resolution of one digit after the decimal place.
Object Description
Index
7450h
Name
PID Proportional Band
Object Type
ARRAY
Data Type
INTEGER16