UMAX130511 Version 1.00A Preliminary Documentation
– May be subject to change
112 - 141
2.4.41. Object 2460h: PID Output Field Value
This read-only output contains the PID control function block FV (as a percentage) that can be used as the
input source for another function block (i.e. analog output.) It will be a value between 0 to 100% as per the
algorithm defined in Figure 14. The physical unit for this object is percentage, and the value is always
interpreted as having a resolution of one digit after the decimal place.
Object Description
Index
2460h
Name
PID Output FV
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
2
Default Value
2
Sub-Index
1h to 2h (x = 1 to 2)
Description
PID
x
Output FV
Access
RO
PDO Mapping
Yes
Value Range
0 to 1000 (0 to 100%)
Default Value
No
2.4.42. Object 2500h: EC Extra Received Process Value
This object provides an extra control source in order to allow other function blocks to be controlled by data
received from a CANopen ® RPDO. It functions similarly to any other writeable, mappable PV object.
Object Description
Index
2500h
Name
EC Extra Received Process Value
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index
0h
Description
Largest sub-index supported
Access
RO
PDO Mapping
No
Value Range
14
Default Value
14
Sub-Index
1h to 14h (x = 1 to 14)
Description
ECx Extra Received Process Value
Access
RW
PDO Mapping
Yes