Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
Contains the result of a disjunction (OR-operation) of all
bits of byte 24 (Maintenance required).
1
(19) = "Bit: Maintenance
requ."
NAMUR mainten. req.
3
In all bits of byte 24, no signals are active (all bits are set
to 0).
0
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation condi-
tions.
Contains the result of a disjunction (OR-operation) of all
bits of bytes 25 to 28 (Out of specification 1 to 4).
1
(18) = "Bit: Out of spec."
NAMUR out of spec.
4
In bytes 25 and 28, no signals are active (all bits are set
to 0).
0
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are tem-
porarily invalid.
Contains the result of a disjunction (OR-operation) of all
bits of bytes 29 and 30 (Function check 1 and 2).
1
(17) = "Bit: Function check"
NAMUR funct. check
5
In bytes 29 and 30, no signals are active (all bits are set
to 0).
0
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Contains the result of a disjunction (OR-operation) of all
bits of byte 23 (Failure).
1
(16) = "Bit: Failure"
NAMUR failure
6
In all bits of byte 23, no signals are active (all bits are set
to 0).
0
Collective signal 05:
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to
NAMUR are present.
Bit 7 is set if bits 0 to 6 are deleted.
1
(15) = "Bit: Device ok"
Device ok
7
Contains the result of a disjunction (OR-operation) of bits
0 to 6 (device status).
0
Byte 6: Operation status
This byte stores information about actuator movement.
Table 7: Byte 6: Operation status
Description
Value
Prm-Text-Def GSD file
Designation
(process representation)
Bit
The actuator is in off-time (e.g. reversing prevention time)
1
(23) = "Bit: Op. pause act-
ive"
Operation pause active
0
No signal
0
The actuator is in an intermediate position e.g. neither in
end position OPEN nor in end position CLOSED.
1
(29) = "Bit: In interm. posi-
tion"
In intermediate pos.
1
No signal
0
The actuator is within the set stepping range.
1
(24) = "Bit: Start step
mode"
Start stepping mode
2
The actuator is outside the set stepping range.
0
No signal (reserved)
—
—
3
Actuator is running (output drive is moving)
Hard wired collective signal consisting of signals:
●
(26)
Running LOCAL
●
(27)
Running REMOTE
●
(28)
Handwheel oper.
1
(25) = "Bit: Actuator run-
ning"
Actuator running
4
No signal
0
25
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Description of the data interface
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...