Table 73: Switchgear
Setting value
Default
Access
Parameters
Type
No.
Data length = 2 bytes
Min = 1 [0.1 s]
3
R
Revers. prevent. time
U16
40-1
Max = 300 [0.1 s]
Min = 31 [Hz]
50
R
Frequency limit
U16
PRM_1329
Max = 70 [Hz]
Min = 5 [Hz]
20
R
Frequency limit
U16
PRM_1343
Max = 30 [Hz]
Table 74: Monitoring functions
Setting value
Default
Access
Parameters
Type
No.
Data length = 18 bytes
0:
Function not active
0
R
Monitor heat. system
enum
41-1
1:
Function active
Min = 600 [0.1 s]
3000
R
Heating sys. mon. time
U16
PRM_3991
Max = 36000 [0.1 s]
0:
Function not active
0
R
Heater monitor
U16
PRM_3172
1:
Function active
0:
Function not active
0
R
Monitor 24 V DC ext.
enum
41-2
1:
Function active
0:
Function not active
1
R/W
Monitor 24 V DC cust.
enum
41-3
1:
Function active
0:
Function not active
1
R
Monitor 24 V AC
enum
41-4
1:
Function active
0:
Function not active
1
R
Monitor 24 V DC intern
enum
41-5
1:
Function active
0:
Function not active
0
R
PTC trip. monit.
enum
41-6
1:
Function active
0:
Function not active
1
R
RTC battery test
enum
41-7
1:
Function active
Min = 500 [0.001 g]
1000
R
Vibration alarm level
U16
PRM_3517
Max = 4000 [0.001 g]
Min = 600 [0.1 s]
3000
R
Heating sys. mon. time
U32
41-8
Max = 36000 [0.1 s]
Table 75: Service interface
Setting value
Default
Access
Parameters
Type
No.
Data length = 22 bytes
_DEVICE-
TAG_
R/W
Device tag
S20
42-1
0:
Control: LOCAL
0
R/W
Service op. mode
enum
42-2
1:
Control: LOC+REM
77
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Appendix
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...