Controls (DPM1 = master of class 1) can only write and read acyclic data via the
active channel. Engineering stations (DPM2 = master of class 2) can use both
channels to read and write acyclic DP-V1 data (writing the same parameter via both
communication channels simultaneously is, however, not possible).
Byte 31 Fieldbus status is used to signal the following communication states of the
two channels to the DCS:
●
Active or passive channel (
Channel 1 active
,
Bit: Channel 2 active
)
●
Profibus DP Watchdog Status (
Channel 1 DataEx
,
Bit: Channel 2 DataEx
)
●
Fault state (
Ch.1 FailState Fieldb.
,
Bit: Chan 2 FailState fieldbus
)
●
Available fieldbus communication (
Channel 1 activity
,
Bit: Channel 2 activity
),
i.e. Profibus Watchdog Status
≠
Baud Search
The DCS may change over the active channel if both channels do not signal a fault
state (neither Global Control Clear nor telegrams with the data length 0) and are in
the DataEx state. Change-over is made during the logical 0–1 change of bits
Fieldbus
channel 1
or
Fieldbus channel 2
in byte 5 of the output data (process representation
output).
Change-over can be initiated both via the active and the passive channel.
Automatic change-over to another channel is performed if either the communication
of the active channel fails or if Fail Safe telegrams (telegrams with the data length
= 0) or Global Control Clear (GC Clear) telegrams are received via the active channel.
Changing channels does not result in a loss of data.
If neither of the channels exchange process data with the controls or if both channels
receive Fail Safe telegrams (telegrams with the data length = 0) or Global Control
Clear (GC Clear) telegrams, the set failure behaviour or EMERGENCY behaviour
is started.
AUMA redundancy II
In general, the actuator decides autonomously which of the Profibus DP
communication channels will be the active channel and therefore be able to operate
the actuator and which channel will be the passive channel only providing feedback
signals of the actuator. Only one slave address can be assigned for both
channels.
Figure 2: Basic structure for AUMA redundancy II
Response path of the active channel
Response path after change-over
The operation of both communication channels is physically separated, however
they are logically and chronologically synchronised.
43
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Description of the data interface
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...