Table 76: Service functions
Setting value
Default
Access
Parameters
Type
No.
Data length = 4 bytes
Min = 32768
-1
R
Create factory settings
I16
45-1
Max = 32767
Min = 32768
-1
R/W
Reset factory settings
I16
45-2
Max = 32767
Table 77: General information
Setting value
Default
Access
Parameters
Type
No.
Data length = 48 bytes
Min = 0
R
Torque fault OPEN
BOOL
44-1
Max = 1
Min = 0
R
Torque fault CLOSE
BOOL
44-2
Max = 1
1:
Local
R
Selector switch
enum
44-3
2:
Off
3:
Remote
Min = 0 [0.1 %]
R
Actual position
U16
44-4
Max = 1000 [0.1 %]
Min = 0 [0.1 %]
R
Torque
U16
44-5
Max = 1000 [0.1 %]
0:
Power Off
R
Operation mode
enum
44-6
1:
EMCY stop
2:
Off
3:
Service
4:
Local
5:
Interlock
6:
EMERGENCY
7:
Remote
8:
Remote II
9:
Fieldbus
10:
Disabled
Min = 0
R
Operation command
DrvCmd4
44-7
Max = 0xFFFFFFFF
Min = 0
R
Running OPEN
BOOL
44-8
Max = 1
Min = 0
R
Running CLOSE
BOOL
44-9
Max = 1
Min = 0
R
Setpoint pos.reached
BOOL
44-10
Max = 1
Min = 0
R
Limit switch OPEN
BOOL
44-11
Max = 1
Min = 0
R
Limit switch CLOSED
BOOL
44-12
Max = 1
Min = 0
R
Torque sw. OPEN
BOOL
44-13
Max = 1
Min = 0
R
Torque sw. CLOSED
BOOL
44-14
Max = 1
78
Actuator controls
Appendix
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...