Setting value
Default
Access
Parameters
Type
No.
0:
Sel. sw. Local
0
R/W
Enable LOCAL
enum
11-3
1:
Sel. sw. Local + Off
0:
Selector switch Local
0
R/W
Priority REMOTE
enum
11-4
1:
Sel. sw. Local + Off
0:
Off
1
R/W
Fieldbus auto enable
enum
11-5
1:
On
Table 53: I/O interface
Setting value
Default
Access
Parameters
Type
No.
Data length = 4 bytes
0:
Off (push-to-run op.)
3
R/W
Self-retaining Remote
enum
12-1
1:
OPEN
2:
CLOSE
3:
OPEN and CLOSE
4:
OPEN & CL w/o STOP
0:
DIR_AUTO
3
R/W
Self-retaining
enum
PRM
4821
1:
DIR_CW
2:
CW
3:
CW and CCW
4:
CW & CCW w/o STOP
0:
Off (push-to-run op.)
0
R/W
Self-retaining Remote II
enum
12-2
1:
OPEN
2:
CLOSE
3:
OPEN and CLOSE
4:
OPEN & CL w/o STOP
Table 54: Profibus DP
Setting value
Default
Access
Parameters
Type
No.
Data length = 4 bytes
Min = 0
126
R/W
DP1 slave address
U16
13-1
Max = 126
Min = 0
126
R/W
DP2 slave address
U16
13-2
Max = 126
Table 55: Positioner
Setting value
Default
Access
Parameters
Type
No.
Data length = 30 bytes
0:
Off
0
R/W
Adaptive behaviour
enum
14-1
1:
Adaptive I
Min = 2 [0.1 s]
5
R/W
Dead time
U16
14-2
Max = 600 [0.1 s]
Min = 0 [0.1 %]
5
R/W
Dead band OPEN
U16
14-3
Max = 100 [0.1 %]
Min = 0 [0.1 %]
5
R/W
Dead band CLOSE
U16
14-4
Max = 100 [0.1 %]
Min = 0 [0.1 %]
5
R/W
Posit. hyst. OPEN
U16
14-5
Max = 50 [0.1 %]
Min = 0 [0.1 %]
5
R/W
Posit. hyst. CLOSE
U16
14-6
Max = 50 [0.1 %]
67
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Appendix
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...