Description
Designation
(process representation)
Prm-Text-Def GSD file
Received setpoint cannot be performed as the positioner is not
available.
Setpoint pos. disabled
(55) = "Bit: Wrong command"
Motor protection tripped.
Thermal fault
(56) = "Bit: Thermal fault"
●
When connecting to a 3-ph AC system and with internal 24 V
DC supply of the electronics: Phase 2 is missing.
●
When connecting to a 3-ph or 1-ph AC system and with external
24 V DC supply of the electronics: One of the phases L1, L2 or
L3 is missing.
Phase fault
(57) = "Bit: Phase fault"
The phase conductors L1, L2 and L3 are connected in the wrong
sequence.
Incorrect phase seq
(58) = "Bit: Wrong phase sequence"
Due to insufficient mains quality, the controls cannot detect the
phase sequence (sequence of phase conductors L1, L2 and L3)
within the pre-set time frame provided for monitoring.
Mains quality
(59) = "Bit: Mains quality"
Torque fault in direction CLOSE
Torque fault CLOSE
(60) = "Bit: Torque fault CLOSE"
Torque fault in direction OPEN
Torque fault OPEN
(61) = "Bit: Torque fault OPEN"
Torque fault in directions CLOSE or OPEN
Torque fault
(62) = "Bit: Torque fault"
Warning: Max. permissible operating time for an operation (OPEN-
CLOSE) exceeded
Op. time warning
(63) = "Bit: Operat. time warning"
Warning: Max. number of motor starts (starts) or max. running time/h
exceeded
Warning on time
(64) = "Bit: On time warning"
The internal 24 V AC voltage supply of the controls has exceeded
the power supply limits.
The 24 V AC voltage supply is used to control the reversing contact-
ors, to assess the thermoswitches, to supply the internal actuator
heater and, as an option, to generate the 115 V AC supply for the
customer.
IE 24 V AC
(65) = "Bit: 24 V AC, internal"
The 24 V DC auxiliary voltage (e.g. for supply of the control outputs)
is outside the supply voltage limits.
24 V DC customer
(66) = "Bit: 24 V DC control volt."
The internal 24 V DC supply voltage of the controls for supply of
the electronic components is outside the supply voltage limits.
24 V DC internal
(67) = "Bit: 24 V DC, internal"
The external 24 V DC voltage supply of the controls has exceeded
the power supply limits.
24 V DC external
(68) = "Bit: 24 V DC, external"
Collective signal 14: Internal error
Internal error
(69) = "Bit: Internal error"
Collective signal 15: Internal warning
Internal warning
(70) = "Bit: Internal warning"
No actuator reaction to operation commands within the set reaction
time.
Wrn no reaction
(71) = "Bit: No reaction"
Incorrect configuration, i.e. the current setting is invalid.
Configuration error
(72) = "Bit: Configuration error"
Parameter not available
Temp. fault controls
(73) = "Bit: Temp. fault controls"
Parameter not available
Temp. fault motor
(74) = "Bit: Temp. fault motor"
Parameter not available
Temp. fault gearbox
(75) = "Bit: Temp.fault gearbox"
Heater failure at actuator (control unit)
Wrn heater
(76) = "Bit: Wrn heater"
Real time clock has not yet been set.
Time not set
(77) = "Bit: RTC not set"
Parameter not available
Wrn humidity
(78) = "Bit: Wrn humidity"
Warning:
Position feedback of actuator was not yet referenced for limit end
positions.
Wrn ref.actual position
(79) = "Bit: WrnRefActPos"
Warning:
Current position feedback signal range is outside the permissible
range.
Wrn range act.pos.
(80) = "Bit: WrnSigRgeActPos"
Warning:
A signal loss has occurred for actuator position feedback.
Wrn sign.loss act.pos.
(81) = "Bit: WrnSigLossActPos"
15
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Commissioning
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...