Table 49: Hardware article no.
Default
Access
Parameters
Type
No.
Data length = 140 bytes
_ ARTNR LC _
R
ArtNo LC
S20
7-1
_ ARTNR LOGIC _
R
ArtNo logic
S20
7-2
_ ARTNR MCM _
R
ArtNo MCM
S20
7-3
_ ARTNR_OPT _
R
ArtNo PSO
S20
7-4
_ ARTNR INTF _
R
ArtNo I/O interface
S20
7-5
_ ARTNR PBD _
R
ArtNo fieldbus
S20
7-6
_ ARTNR MWG _
R
ArtNo MWG
S20
7-7
_ ARTNR FQM _
R
Art. no. FQM Ctrl
S20
PRM_5083
_ ARTNR MCTRL_
R
ArtNo motor ctrl
S20
PRM_5094
Table 50: Type of seating
Setting value
Default
Access
Parameters
Type
No.
Data length = 4 bytes
0:
Limit
0
R/W
End position CLOSED
enum
9-1
1:
Torque
0:
Limit
0
R/W
End position OPEN
enum
9-2
1:
Torque
Table 51: Torque switching
Setting value
Default
Access
Parameters
Type
No.
Data length = 12 bytes
0:
Function not active
1
R/W
Torque by-pass
enum
10-1
1:
Function active
Min = 0 [0.1 s]
0
R/W
Torque by-pass [s]
U16
10-2
Max = 50 [0.1 s]
0:
Function not active
1
R/W
Torque limitation
enum
PRM_5161
1:
Function active
Min = 100 [%]
0
R/W
Torque peak [%]
I16
PRM_5162
Max = 150 [%]
Min = 0 [Nm]
20
R/W
Trip torque CLO [Nm]
U16
10-3
Max = 65535 [Nm]
Min = 0 [Nm]
20
R/W
Trip torque OPEN [Nm]
U16
10-4
Max = 65535 [Nm]
Min = 20 [%]
80
R/W
Wrn torque CLOSE
I16
10-5
Max = 100 [%]
Min = 20 [%]
80
R/W
Wrn torque OPEN
I16
10-6
Max = 100 [%]
Table 52: Local controls
Setting value
Default
Access
Parameters
Type
No.
Data length = 10 bytes
0:
Off (push-to-run op.)
3
R/W
Self-retaining Local
enum
11-1
1:
OPEN
2:
CLOSE
3:
OPEN and CLOSE
4:
OPEN & CL w/o STOP
0:
Off
0
R/W
Local STOP
enum
11-2
1:
Sel.sw.Local + Remote
66
Actuator controls
Appendix
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...