Table 84: Profibus DP2
Setting value
Default
Access
Parameters
Type
No.
Data length = 15 bytes
Min = 0
R
DP2 slave address
U8
56-1
Max = 126
0:
12 Mbit/s
R
DP2 baud rate
enum
56-2
1:
6 Mbit/s
2:
3 Mbit/s
3:
1.5 Mbit/s
4:
500 kbit/s
5:
187.5 kbit/s
6:
93.75 kbit/s
7:
45.45 kbit/s
8:
19.20 kbit/s
9:
9.6 kbit/s
15:
Not available
0:
Baud search
R
DP2 watchdog status
enum
56-3
1:
Baud control
2:
DP control
0:
Wait Prm
R
DP2 Profibus status
enum
56-4
1:
Wait Cfg
2:
Data Ex
0:
GC Clear inactive
R
DP2 GC clear
enum
56-5
1:
GC Clear active
0:
Data length 0 inactive
R
DP2 data length 0
enum
56-6
1:
Data length 0 active
0:
GC Freeze inactive
R
DP2 GC freeze
enum
56-7
1:
GC Freeze active
0:
GC Sync inactive
R
DP2 GC sync
enum
56-8
1:
GC Sync active
Table 85: Profibus details
Setting value
Default
Access
Parameters
Type
No.
Data length = 36 bytes
Min = 0
R
DP-V1 control
BOOL
57-1
Max = 1
Min = 0
R
DP-V1 active
BOOL
57-2
Max = 1
Min = 0
R
Channel 1 active
BOOL
57-3
Max = 1
Min = 0
R
Channel 2 active
BOOL
57-4
Max = 1
0:
None
R
Primary
enum
57-5
1:
Channel 1
2:
Channel 2
0:
None
R
Backup
enum
57-6
1:
Channel 1
2:
Channel 2
81
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Appendix
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...