Product Features
141
© 2017, ATEÏS, member of PAX ProAV Group
the possible circumstances of facing detected fault with corresponding LED.
Output voltage fault:
It is signalled by a yellow LED and it's available on dry contact (fail-safe) for remote monitoring.
If there's no voltage on one or more output, all the five outputs are checked. Each dry contact is with
a three pole SPDT switch (C-NC-NO), allowing 1A @ 24Vdc or 0,5A @ 120Vac.
Battery fault (back-up source):
It is signalled by a yellow LED and it's available on dry contact (fail-safe) for remote monitoring.
o
If the battery voltage < 21,6V ±3 %.
o
If the internal impedance is too high (test every 4 hours maximum on a charged battery). The
impedance limit value is 50 mW±10 %.
o
If the battery isn't under operation, the system shall continue proceeding the following
manner: every 30 seconds for the first 20 minutes after commissioning and every 15 minutes
after. As soon as a fault is detected, the test shall be continue proceeding every 30 seconds
until 20 minutes after the fault disappears.
Mains fault (normal source):
It is signalled by a yellow LED and it's available on dry contact with delay (fail-safe) for remote
monitoring.
o
If the mains is not serve or < 195 V.
o
If the mains fuse is blown.
o
If the charger is faulty.
3.1.21.1.2 Real Panel
Main power socket
Auxiliary output terminals
Battery terminal
Output contacts
Main output terminals
Temperature sensor
Connection specifications
Mains: 2.5 mm²
Battery: 16 mm²
‘Amplifiers’ load (outputs 1 and 2): 16 mm²