supply the minimum amount of power for a set amount of time. With SONAES battery chargers, it
provides you with a battery calculator program which determines the exact capacity.
This product is a Power Supply Equipment (PSE) as defined in the EN 54-4 standard. It is designed to be
connected to the 230 V public distribution network. To avoid any risk of electric shock, all interventions
must be carried out with disconnected mains supply. A bipolar isolating switch must be installed likewise
in the batteries circuit. Interventions with the equipment switched on are authorized only when it is
impossible to switch the equipment off. The operation must only be performed by qualified personnel.
3.1.21.2.1 Front Panel
When the 3 LEDs light up in green, it indicates that your apparatus is in correct operation. Here are
the possible circumstances of facing detected fault with corresponding LED.
Output voltage fault:
It is signalled by a yellow LED and it's available on dry contact (fail-safe) for remote monitoring.
If there's no voltage on one or more output, all the five outputs are checked. Each dry contact is with
a three pole SPDT switch (C-NC-NO), allowing 1A @ 24Vdc or 0,5A @ 120Vac.
Battery fault (back-up source):
It is signalled by a yellow LED and it's available on dry contact (fail-safe) for remote monitoring.
o
If the battery is not serve.
o
If the internal impedance is too high .
o
If the battery voltage < 23,5 V ±3 %. resp. 47,0 V ±3 % mains present.
Mains fault (normal source):
It is signalled by a yellow LED and it's available on dry contact with 5 sec delay (fail-safe) for remote
monitoring.
o
If the mains is not serve or < 185 V+/-5% as long as the charger was switched off, <165V+/-5%
if it was switched on.
o
If the mains fuse is blown.
o
If the charger is faulty.
o
If the internal temperature is too high.