5 - 10
Chapter Five
Code
Description
Possible causes / actions
E51
Supply-on-test over voltage.
The Supply-on-Test voltage has exceed the load bank limits.
•
Check the Supply-on-Test voltage.
Note that a low Supply-on-Test frequency may also cause an
over voltage error. The maximum voltage is frequency depend-
ant for resistive/reactive load banks.
Check the load bank specification for voltage and
frequency limits.
E52
Supply-on-test incorrectly wired.
The Supply-on-Test is wired incorrectly when using remote
Modbus load control.
•
Check the Supply-on-Test connection, possible phase rota-
tion or phase missing.
E60
E61
Ring main unit 0 tripped.
Ring main unit 1 tripped.
The load bank Supply-on-Test ring main unit is tripped.
•
Ensure the ring main unit is closed before pressing the load
bank Start button.
•
If the load bank ring main unit trips whilst on load, verify the
cause before re-closing.
E90
No valid load bank setup.
E91
Self test failed.
E99
Unknown error.
If you are unable to rectify the problem call Froment on +44 (0) 1780 480033 or email
[email protected] for assistance.