To edit the test sequence:
1. Press F1 (NEXT) to choose the sequence stage to be programmed.
2. Press F3 (SELECT) to choose the value to be changed.
3. Use the
+ and - keys to adjust the value.
4. Pressing F2 (COPY) will copy the current value to the next sequence stage.
5. Press F3 (SELECT) to choose the next value to be changed.
6. When all values are edited, press F1 (NEXT) to choose the next sequence stage to be
programmed.
7. Press F4 (OK) to return to the Test pages when programming is complete.
Note: Setting the time
value to 0 will cause the
Hand-held to ignore the
step. Setting the load
percentage for the first
step at 0 will allow the
fan to start without any
load being applied.