5 - 9
Maintenance & Troubleshooting
Code
Description
Possible causes / actions
E24
Fan supply voltage and/or frequency limits exceeded
on pressing the load bank start button.
Fan supply voltage or frequency is out of limits.
•
Check control voltage and frequency. If the generator rating
is incorrect run the load bank from an external supply.
•
Check the Fans and Controls Supply Selector switch is in
the correct position.
E25
Fan supply check shows phase missing.
Fan supply phase is missing.
•
Check control phases. If the generator rating is incorrect
run the load bank from an external supply.
•
Check the fans and controls supply selector switch is in the
correct position.
E26
E27
E28
E29
No running signal for Fan 0.
No running signal for Fan 1.
No running signal for Fan 2.
No running signal for Fan 3.
Load bank cooling fan is not running or fan contactor not ener-
gising
•
Check the fan contactor is energising and the auxiliary
contactor is operating.
•
Check the HV transformer compartment cooling fans.
E30
E31
E32
E33
Overload tripped on Fan 0.
Overload tripped on Fan 1.
Overload tripped on Fan 2.
Overload tripped on Fan 3.
A Fan overload has tripped on over current.
•
Check the fan is not obstructed, the inlet is clear and is free
to rotate.
•
Confirm the over load is set to the correct current setting
by referring to the load bank drawings.
E34
Fan supply voltage and/or frequency limits
exceeded.
Fan supply voltage or frequency is out of limits.
•
Check control voltage and frequency. If the generator rating
is incorrect run the load bank from an external supply.
•
Check the Fans and Controls Supply Selector switch is in
the correct position.
E40
E41
E42
E43
Air flow failure on sensor/circuit 0.
Air flow failure on sensor/circuit 1.
Air flow failure on sensor/circuit 2.
Air flow failure on sensor/circuit 3.
No air flow detected when the load bank fans are running.
•
Check the fan or duct is not obstructed.
•
Verify the airflow direction - the air should exhaust from the
elements., not from the fan.
•
Check the air flow sensor is operating correctly.
E44
E45
E46
E47
Cover closed on duct 0.
Cover closed on duct 1.
Louvre 0 failed to open.
Louvre 1 failed to open.
The duct cover(s) or louvre(s) are closed.
•
Open the duct covers or louvres before pressing the load
bank Start button.
•
Check the proximity detectors for correct operation.
E50
Supply-on-test failure while on load.
The Supply-on-Test failed whilst load was applied. Any load
applied has been removed and the load bank has gone to an
error state.
This option can be enabled in the load bank to avoid re-starting
a generator on load.
Содержание Froment 8800 Series
Страница 1: ...8800 SERIES High Voltage Load Banks User Manual Power Technologies ...
Страница 2: ......
Страница 10: ......
Страница 42: ...Load Bank Installation and Setup 2 14 ...
Страница 106: ...A 4 Appendices Figure A 5 8800 Transformer view ...
Страница 110: ...A 8 Appendices Transformer Maintenance Schedule ...