Leakage of SF6 (Sulfur Hexaflouride) gas
In the extremely unlikely event of a gas leak contact your local Schneider Electric office or
UK customer service team immediately. New SF6 gas is non-toxic and non-combustible.
However when exposed to an electric arc SF6 breaks down and becomes toxic. Ensure the
SF6 gas dial is in the green zone. Do not operate the load bank if the SF6 gas levels are
not sufficient.
Service life
If correctly installed and maintained the Ringmaster range of switchgear has a service life
expectancy of 25 years.
Transformer Maintenance
Please see appendix A-8 for full transformer maintenance schedule.
Fault Finding
The following chart covers some of the typical faults you might encounter on the load
bank and some possible solutions.
Fault
Possible Causes
Possible Solutions
Cooling fan does not start or run
Correct operation.
•
The cooling fan may not run until load is
applied. Apply the load and verify that the fan
starts.
No power to fan.
•
Check the fan and control isolator switch is in
the correct position and the Start button has
been pressed.
•
Confirm that the control supply fuses are not
blown.
Fan thermal overload tripped.
•
Allow the load bank to cool, and then stop the
load bank. Press the reset button followed by
the Start button.
•
Check that the fan is not obstructed and that
it is free to rotate. Check the motor current
and overload setting.
No load is being applied
Supply-on-test is not switched on.
•
Confirm that the Supply-on-Test circuit break-
er is switched on.
•
Ensure that the load bank RMU is closed.
Load bank over temperature trip.
•
Allow the load bank to cool and then reset.
•
Check that the airflow through load bank is
unobstructed.
•
Check for any signs of hot air re circulation.
•
Check the transformer is not over
temperature.
Faulty or damaged connecting lead
•
Check that the Hand-held lead and connectors
are not damaged.
5 - 5
Maintenance & Troubleshooting
Содержание Froment 8800 Series
Страница 1: ...8800 SERIES High Voltage Load Banks User Manual Power Technologies ...
Страница 2: ......
Страница 10: ......
Страница 42: ...Load Bank Installation and Setup 2 14 ...
Страница 106: ...A 4 Appendices Figure A 5 8800 Transformer view ...
Страница 110: ...A 8 Appendices Transformer Maintenance Schedule ...