2 - 12
Load Bank Installation and Setup
System Monitor Control (HMI)
Alternately the load bank can be controlled using the load bank system monitor, this is a
touch screen HMI interface panel located on the internal control cabinet door.
This can also be used remotely by connecting into the RJ45 Ethernet connector located on
the external power inlet compartment. You will need to use a third party software package,
provided with the load bank, for this mode of control.
Figure 2-8
The RJ45 ethernet socket located on the external power inlet compartment.
Optional Remote Connections
A ten pole connector is fitted on the external power inlet compartment. This provides the
user with options to start, stop and reset faults for the load bank from a remote location.
Also included is a remote trip for the ring main unit and a signal to indicate if the load bank
is running.
Figure 2-10
The ten pole connector and table of connections definitions.
Note: If the remote stop
signal is not required
then this must be linked
out. Poles 1 & 2.
6
7
8
9
10
1
2
3
4
5
Terminals
Function
Required
contact type
Running state
Voltage
1 & 2
Remote
Stop
N/C contact
Momentary open to stop
load bank.
24VDC
3 & 4
Remote
start
N/O contact
Momentary close to start-
load bank.
24VDC
5 & 6
Remote
reset
N/O contact
Momentary close to reset
fault.
24VDC
7 & 8
RMU Trip
N/O contact
Momentary close to trip
HV Ring Main Unit (RMU).
24VDC
9 & 10
Load bank
running
N/O contact
Closed when running.
Volt
Free
Содержание Froment 8800 Series
Страница 1: ...8800 SERIES High Voltage Load Banks User Manual Power Technologies ...
Страница 2: ......
Страница 10: ......
Страница 42: ...Load Bank Installation and Setup 2 14 ...
Страница 106: ...A 4 Appendices Figure A 5 8800 Transformer view ...
Страница 110: ...A 8 Appendices Transformer Maintenance Schedule ...