4 - 16
Options 1 - Control:
Figure 4-14
The Options 1 page.
The control options change the Hand-held’s load control behaviour.
Ramp Down on Reject.
Protects the Supply-on-Test from damage by removing the load
gradually when the
O key is pressed. When this option is selected the load will ramp down
in ten equal steps over a period of 12 seconds. Press
O a second time to reject the load
immediately. The Hand-held’s LED will blink rapidly during the ramp down period.
Cyclic Auto Test.
When the automatic test sequence reaches the last step it will restart
the sequence at step 1.
Show Total Test Time.
If this option is selected the status line on the Test pages will show
the total accumulated test time. Otherwise it will show the time since the current load was
applied.
Options 2 - Display:
Figure 4-12
The Options 2 page.
Language.
Select the default language. Five languages are supported as standard. These
are English, French, German, Spanish and Italian. Changing the language setting will
change all of the text on the display, including function key labels and help messages.
Load Control.
Lets you override the default increment for load selection. The default
resolution for load control is determined by the load bank size and minimum load step.
For example it could be in tenths of kW or whole kW or tens of kW. On this page you can
select one more or one less resolution then the default selection by setting these to “Fine”
or “Coarse”.
Hand-held Reference Guide
Содержание Froment 8800 Series
Страница 1: ...8800 SERIES High Voltage Load Banks User Manual Power Technologies ...
Страница 2: ......
Страница 10: ......
Страница 42: ...Load Bank Installation and Setup 2 14 ...
Страница 106: ...A 4 Appendices Figure A 5 8800 Transformer view ...
Страница 110: ...A 8 Appendices Transformer Maintenance Schedule ...