5 - 8
Errors
If an error occurs the load bank Reset button lamp will begin to flash and a three step
code sequence will be continuously displayed in the same way as a warning. Again, each
character is displayed for 500ms with the code repeating every 2 seconds. The end of the
sequence is indicated with the decimal point only.
When an error occurs any load applied will be dropped and, if the fault is not cooling
related, the load bank fan will continue to run for the preset cooling period.
After rectifying the fault press the Reset button to clear the error. The Reset lamp will stop
flashing and will be continuously illuminated. Press the Start button to restart the load
bank.
The three digit error codes all begin with an ‘E’ as follows:
Note:
The error mes-
sages displayed are
dependant on the load
bank configuration. For
example, if the load
bank has no duct covers
fitted then any associ-
ated errors will not be
monitored or reported.
Chapter Five
Code
Description
Possible causes / actions
E01
Stop pressed.
Start button has not been pressed or was pressed before the
load bank had performed its power on self-test (both Start and
Reset illuminated).
•
Wait until the Reset button only is illuminated before press-
ing the Start button.
External emergency stop buttons (if fitted) are depressed
•
Release all emergency stop buttons and press the Start
button.
E02
Lost communications with Hand-held (or PC).
Hand-held (or Sigma PC system) has disconnected from load
bank while a load is applied.
Hand-held or load bank interconnecting cable fault.
•
Check and replace.
E03
Load contactor switching fault.
A load contactor switching fault has been detected.
A load step contactor or relay is energised but no load is applied.
No response from the load contactor or relays when load is
requested.
E10
E11
E12
E13
Over temperature on sensor/circuit 0.
Over temperature on sensor/circuit 1.
Over temperature on sensor/circuit 2.
Over temperature on sensor/circuit 3.
Load bank is over temperature.
•
Allow the load bank to cool, and then press Stop and Start
buttons.
•
Ensure that the load bank ambient temperature is not ex-
ceeded and check that the hot air discharge is not recircu-
lating.
•
Ensure the HV transformer is not over temperature.
More than one over temperature trip may be fitted. These devic-
es will automatically reset when they cool down.
E20
Fan supply rotation check failed
The fan supply phase rotation detection failed when starting the
load bank Fan(s).
•
Check the fan supply for a missing phase or single phase
connection.
•
Check the Fans and Controls Supply Selector switch is in
the correct position.
Содержание Froment 8800 Series
Страница 1: ...8800 SERIES High Voltage Load Banks User Manual Power Technologies ...
Страница 2: ......
Страница 10: ......
Страница 42: ...Load Bank Installation and Setup 2 14 ...
Страница 106: ...A 4 Appendices Figure A 5 8800 Transformer view ...
Страница 110: ...A 8 Appendices Transformer Maintenance Schedule ...