CFS300 SERIES OPERATION MANUAL
SECTION 6: FRONT PANEL OPERATION
Entire Contents Copyright
2016 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CFS300 Series Power Source Operation Manual
Page 78 of 156
6.10.15
Function Settings (Output Phase Mode)
Press the “
Next
” soft key if needed to advance to the next parameter, the “
Function
”
setting. The Function parameter determines the output mode.
When in DC mode, the output is fixed to single phase (1ø2W) and cannot be changed. When
in AC, the following selections are available:
1ø2W
Single Phase Output
. Output terminals are wired as Line to Neutral. Same mode
applies when in DC mode.
3ø4W
Three Phase Output
. Output terminals are wired as A, B, C with respect to
Neutral. Phase offset for phase B = 120° and for phase C = 240° with respect to
phase A.
1ø3W
Split Phase Output
. Output terminal are wired as L1 – N and L2 – N. Phase
offset of L2 = 180° with respect to L1.
No internal configuration changes, jumpers or dip switches need to be set to change phase
modes as all internal connections are controlled by firmware.