CFS300 SERIES OPERATION MANUAL
SECTION 7: REMOTE PROGRAMMING
Entire Contents Copyright
2016 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CFS300 Series Power Source Operation Manual
Page 115 of 156
7.7
Parameter Setup Command and Query Syntax
These commands are used to modify individual test parameters within each step. Many of
these commands require a parameter value to be sent with the command. The
corresponding query command will return the parameter setting in effect. Parameter values
are sent as numeric values so no unit info like V or Hz should be appended. Also, when the
query commands are sent, the responses will not include any unit characters.
Command
Description
Value
Unit
AR {0|1|2}
Set Auto Run
0=PROGRAM,1=MANUAL, 2=DC
AR?
Return Auto Run Value
0~2
MC <value>
Set Memory Cycle Value
0~9999 ,0=Contine,1=OFF
MC?
Return Memory Cycle Value
0-9999
MEMORY
<value>
Memory Number
1-50
MEMORY?
Return Memory Number
1-50
STEP <value>
Step Number
1-9
STEP?
Return Step Number
1-9
VOLT <value>
Set Voltage Value
AC: 5.0-300.0 / DC: 5.0-420.0
V
VOLT?
Return Voltage
AC: 5.0-300.0 / DC: 5.0-420.0
V
RANG {1|0}
Range Set
0=HIGH,1=AUTO
RANG?
Return Range Set
0-1
FREQ <value>
Input Frequency Value
40.0~1000
Hz
FREQ?
Return Frequency Value
See Section 5 for range
Hz
AHI <value>
Set Current High Limit
See Section 5 for range
A
AHI?
Return Current High Limit
See Section 5 for range
A
ALO <value>
Set Current Low Limit
See Section 5 for range
A
ALO?
Return Current Low Limit
See Section 5 for range
A
APHI <value>
Set Current Peak High Limit
See Section 5 for range
A
APHI?
Return Current Peak High Limit
See Section 5 for range
A
APLO <value>
Set Current Peak Low Limit
See Section 5 for range
A
APLO?
Return Current Peak Low Limit
See Section 5 for range
A
PHI <value>
Set Power High Limit
See Section 5 for range
W
PHI?
Return Power High Limit
See Section 5 for range
W
PLO <value>
Set Power Low Limit
See Section 5 for range
W
PLO?
Return Power Low Limit
See Section 5 for range
W
PFHI <value>
Set Power Factor High Limit
0.000~1.000
PFHI?
Return Power Factor High Limit
0.000~1.000
PFLO <value>
Set Power Factor Low Limit
0.000~1.000
PFLO?
Return Power Factor Low Limit
0.000~1.000
CFHI <value>
Set Crest Factor High Limit
0.00~10.00
CFHI?
Return Cest Factor High Limit
0.00~10.00
CFLO <value>
Set Crest Factor Low Limit
0.00~10.00
CFLO?
Return Crest Factor Low Limit
0.00~10.00
VAHI <value>
Set Apparent Power High Limit
See Section 5 for range
VA
VAHI?
Return Apparent Power High Limit See Section 5 for range
VA
VALO <value>
Set Apparent Power Low Limit
See Section 5 for range
VA
VALO?
Return Apparent Power Low Limit See Section 5 for range
VA