CFS300 SERIES OPERATION MANUAL
SECTION 5: UNPACKING & INSTALLATION
Entire Contents Copyright
2016 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CFS300 Series Power Source Operation Manual
Page 46 of 156
5.8.5
Recommend AC Input Wire Gauges
Depending on your local utility power voltage and phase configurations, make sure you
configure the AC input for the correct mains voltage and phasing.
Recommended Wire Gauges CFS330 AC Input
AC Configuration
A-L, B-L, C-L
A-N, B-N, C-N
GND
Single Phase
2 Wire+Gnd
10 AWG (Ø 2. 59 mm)
A-L, B-L, C-L Short
10 AWG (Ø 2. 59 mm)
A-N, B-N, C-N Short
12 AWG THWN, Copper
(Ø 2.05 mm)
Three Phase Delta
3 Wire+Gnd
12 AWG THWN,
Copper (Ø 2.05 mm)
A-L/A-N, B-L/B-N, C-
L/C-N Short
10 AWG THWN, Copper
(Ø 2. 59 mm)
Single Phase Wye
4 Wire+Gnd
16 AWG THWN,
Copper (Ø 1.29 mm)
10 AWG (Ø 2. 59 mm)
A-N, B-N, C-N Short
10 AWG THWN, Copper
(Ø 2. 59 mm)
Table 6-4: AC Input Wire Gauges by Configuration
5.9
Cleaning
To clean this product, use a soft or slightly damp cloth.
CAUTION
BEFORE you clean the unit, disconnect from mains power.
・
Please do NOT use any organic solvent capable of changing the nature of the
plastic such as benzene or acetone.
・
Please ensure that no liquid is allowed to penetrate this product.