SECTION 5: UNPACKING & INSTALLATION
Entire Contents Copyright
2016 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CFS300 Series Power Source Operation Manual
Page 44 of 156
5.8.2
CFS360 AC Input Connections
The CFS360 requires either single or three phase AC input power. Phase configurations are
set using the shorting bars provided in the ship kit. Figure 6-6 below shows the two shorting
bars installed for single phase input.
Supported AC input voltage ranges are 200V to 240V for single phase or three phase delta
input and 364V to 420V for three phase Wye input. The AC input terminal block must be
configured for the available line voltage using the included shorting bars.
Input frequency is from 47 to 63 Hz. The AC input terminal blocks are located on the rear
panel, to the right of the output terminal block.
Note:
Do not connect any CFS300 Series unit to the mains if the AC input voltage, phasing
and frequency does not match.
Safety Cover:
Before connecting any AC line cord, make sure the cord is routed through
the AC input side strain relief of the provided safety cover. After AC input and any
output connections have been made, the safety cover must be installed using the
slots and two screws provided. The figure on the right shows the correct installation
of the safety cover.
Figure 6-6: CFS360 AC Input Terminal Location