7.6
Three Phase Mode Commands
The commands listed in the tables below apply only to three phase mode operation and AC
mode. 3ø4W).
7.6.1
Voltage Measurement Commands – 3 Phase
Command
Description
AC Program
AC Manual
Unit
TDA?
Testing R-N meter data
Memory, Step, Status,
Freq, Volt, Curr,
Power, APeak, PF, Q,
CF, VA, Timer
Memory,Status,
Freq,Volt,Curr,
Power,APeak,
PF,Q,CF,VA
V
TDB?
Testing S-N meter data
V
TDC?
Testing T-L2 meter data
V
TDE?
Testing RS, RT and ST Line to
Line Voltage meter data
V
RDA XX?
Results AØ meter data
V
RDB XX?
ResultsBØ meter data
V
RDC XX?
Results CØ meter data
V
RDE XX?
Results ΣØ meter data
V
Note:
These commands perform the same function as those described in the previous
section but apply to R-N, S-N and T-N measurements respectively.
TDA?
Read the selected Phase A meter values while a test is in process. Query only available in AC
Program mode and AC Manual mode.
TDB?
Read the selected Phase B meter values while a test is in process. Query only available in AC
Program mode and AC Manual mode.
TDC?
Read the selected Phase C meter values while a test is in process. Query only available in AC
Program mode and AC Manual mode.
TDE?
Read the total (Phase A + B + C) meter values while a test is in process. Query only available
in AC Program mode and AC Manual mode.
RDA XX?
Read the selected Phase A results once a test has completed. Query only available in AC
Program mode and AC Manual mode.
RDB XX?
Read the selected Phase B results once a test has completed. Query only available in AC
Program mode and AC Manual mode.
RDC XX?
Read the selected Phase C results once a test has completed. Query only available in AC
Program mode and AC Manual mode.
RDE XX?
Read the selected total (Phase A + B + C) results once a test has completed. Query only
available in AC Program mode and AC Manual mode.