DNP3 Operation
Document No. D109-010
Page 67 of 108
Revision 1.15
In Slate the Target Tag selected must be the Tag or Array with Data Type
AparianDNP3Analog32Flag
as shown below.
Figure 5.4. – Selecting the correct tag from Slate’s Tag Browser.
The same procedure can be followed for numerous other DNP3 Group and Variation
combinations.
NOTE
: If the user does not use the correct UDT the DNP3 Router will either
abandon the routing procedure once it detects the data types are different
(the Logix Data Type Mismatch statistic will increase) or incorrect data will be
received by the Logix Controller.
5.2.
ANALOG/BINARY OUTPUT COMMANDS
The select/operate, direct-operate, and direct-operate with no response DNP3 application
functions (which will collectively be referred to as operate commands) are command based
functions. Unlike a read function these functions only execute when the DNP3 Master triggers
a change (e.g. open a relay or change an analog output). These functions are typically used
for Control Relay Output Blocks (CROB) and Analog Output Blocks (AOB). The three functions
are described below: